Plan Review Notes
Plan Review Notes For Permit 14110798
Permit Number 14110798
Review Stop E
Sequence Number 2
Notes
Date Text
2015-01-08 16:41:371/8/2015
 PROJECT: PB MOTOR CARS
 PERMIT#: 14110798
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE REVISED ELECTRICAL RISER DIAGRAM WITH WIRE
 SIZES , GROUNDING ELECTRODE SYSTEM WITH ELECTRODES AND
 ELECTRODE CONDUCTOR SIZES.
  
 2) PROVIDE CIRCUITRY ON THE FLOOR PLAN TO COINCIDE WITH
 THE CIRCUITRY IN THE PANEL SCHEDULES PROVIDED.
  
 3) PROVIDE THE REQUIRED GFI WITHIN SIGHT OF MECHANICAL
 EQUIPMENT. NEC 210.63 SEE 210.8(A)(3),
  
 4) ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH
 GROUND FAULT CIRCUIT INTERRUPTER PROTECTION. NEC 422.52
  
 5) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR FIRE ALARM, NETWORK, DATA, AND,
 COMMUNICATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  