Plan Review Notes
Plan Review Notes For Permit 14110798
Permit Number 14110798
Review Stop P
Sequence Number 1
Notes
Date Text
2014-11-27 05:19:341) SUBMIT AN OVERALL FLOOR PLAN THAT SHOWS THE LOCATION
 OF THE RESTROOMS BEING RENOVATED. WPB AMEND. TO 2010
 FBC SEC.107.2.1.
 2) THE PLANS ONLY SHOW A MEN'S RESTROOM BEING
 RENOVATED. IS THERE A FEMALE RESTROOM BEING RENOVATED?
 IF SO, SUBMIT PLANS FOR THAT RESTROOM RENOVATION.
 3) INDICATE ON THE PLANS THE SPECIFIC SCOPE OF WORK TO
 BE DONE TO THIS RESTROOM. IS IT NEW OR EXISTING? ARE
 JUST THE PLUMBING FIXTURES BEING REPLACED? THE PLANS
 ARE VAGUE AS TO THE SCOPE OF WORK BEING DONE. WPB
 AMEND. TO 2010 FBC SEC.107.2.1.
 4) SUPPLY ELEVATION DETAILS FOR THE MOUNTING HEIGHTS OF
 ALL APPURTENANCES AND FIXTURES IN THE RESTROOM.
 MOUNTING HEIGHTS SHALL COMPLY WITH THE 2010 FL.
 ACCESSIBILITY CODE. CHAPTER 3 AND CHAPTER 6.
 5) SHOW THE REQUIRED CLEAR FLOOR SPACES FOR THE
 LAVATORY AND THE WATER CLOSET ON THE PLANS. COMPLY WITH
 FAC SECS.306 & 604.
 6) THE DRINKING FOUNTAIN/WATER COOLER CANNOT BE LOCATED
 IN THE RESTROOM PER THE 2010 FPC SEC. 410.2.
 7) SHT. M-1 - SIZE ALL SECTIONS OF THE VENT SYSTEM.
 COMPLY WITH FPC TABLE 916.1.
 8) SIZE THE WET SECTION OF ALL WASTE /SOIL STACKS.TABLE
 710.1.
 9) CLEANOUTS ARE REQUIRED IN THE BASE OF ALL STACKS PER
 FPC SEC. 708.3.4.
 10) SUBMIT A WATER RISER DIAGRAM FOR ANY CHANGES BEING
 MADE TO THE PIPING SYSTEM. WPB AMEND. TO 2010 FBC SEC.
 107.3.5.1.3.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  