| Date |
Text |
| 2014-11-27 05:19:34 | 1) SUBMIT AN OVERALL FLOOR PLAN THAT SHOWS THE LOCATION |
| | OF THE RESTROOMS BEING RENOVATED. WPB AMEND. TO 2010 |
| | FBC SEC.107.2.1. |
| | 2) THE PLANS ONLY SHOW A MEN'S RESTROOM BEING |
| | RENOVATED. IS THERE A FEMALE RESTROOM BEING RENOVATED? |
| | IF SO, SUBMIT PLANS FOR THAT RESTROOM RENOVATION. |
| | 3) INDICATE ON THE PLANS THE SPECIFIC SCOPE OF WORK TO |
| | BE DONE TO THIS RESTROOM. IS IT NEW OR EXISTING? ARE |
| | JUST THE PLUMBING FIXTURES BEING REPLACED? THE PLANS |
| | ARE VAGUE AS TO THE SCOPE OF WORK BEING DONE. WPB |
| | AMEND. TO 2010 FBC SEC.107.2.1. |
| | 4) SUPPLY ELEVATION DETAILS FOR THE MOUNTING HEIGHTS OF |
| | ALL APPURTENANCES AND FIXTURES IN THE RESTROOM. |
| | MOUNTING HEIGHTS SHALL COMPLY WITH THE 2010 FL. |
| | ACCESSIBILITY CODE. CHAPTER 3 AND CHAPTER 6. |
| | 5) SHOW THE REQUIRED CLEAR FLOOR SPACES FOR THE |
| | LAVATORY AND THE WATER CLOSET ON THE PLANS. COMPLY WITH |
| | FAC SECS.306 & 604. |
| | 6) THE DRINKING FOUNTAIN/WATER COOLER CANNOT BE LOCATED |
| | IN THE RESTROOM PER THE 2010 FPC SEC. 410.2. |
| | 7) SHT. M-1 - SIZE ALL SECTIONS OF THE VENT SYSTEM. |
| | COMPLY WITH FPC TABLE 916.1. |
| | 8) SIZE THE WET SECTION OF ALL WASTE /SOIL STACKS.TABLE |
| | 710.1. |
| | 9) CLEANOUTS ARE REQUIRED IN THE BASE OF ALL STACKS PER |
| | FPC SEC. 708.3.4. |
| | 10) SUBMIT A WATER RISER DIAGRAM FOR ANY CHANGES BEING |
| | MADE TO THE PIPING SYSTEM. WPB AMEND. TO 2010 FBC SEC. |
| | 107.3.5.1.3. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |