| 2014-12-04 10:29:59 | BUILDING PLAN REVIEW |
| | PERMIT: 14110798 |
| | ADD: 915 S. DIXIE HWY. |
| | CONT: OVERLAND |
| | TEL: (561)683-3210 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. DEC. 04/ 2014 |
| | ACTION: DENIED |
| | |
| | 1A) SHEET 3 OF 4 THE MEETING ROOM SHOWS THE SCOPE OF |
| | WORK IN THE MEETING ROOM AS WELL AS IN THE LOCKER ROOM. |
| | THE DOOR THAT LEADS FROM THE MEETING ROOM DOES NOT HAVE |
| | THE REQUIRED 18 INCHES ON THE LATCH SIDE OF THE DOOR. |
| | PLEASE SEE 2010 FL ACC. CODE 404.2.4.1 & TABLE |
| | 404.2.4.1. |
| | |
| | 1B) THE DOOR THAT LEADS FROM THE LOCKER ROOM TO THE |
| | EXISTING OFFICE ONLY HAS LESS THAN1 FOOT CLEARANCE FROM |
| | THE LOCKER TO THE EDGE OF THE DOOR, LATCH SIDE. |
| | NOTE THE PLANS DO NOT INDICATE IF THERE IS A DOOR |
| | CLOSER AND LATCH ON THIS DOOR? SEE 2010 FL. ACCESS. |
| | CODE FIGURE 404.2.4.1 (C). |
| | |
| | 1C) THE PERMIT INDICATES THE PERMIT VALUE OF |
| | $80,000.00, THE 2010 FL ACCESS. CODE 202.4.1 |
| | DISPROPORTIONATE COST REQUIRES 20% OF THE CONTRACT |
| | VALUE TO BE ACCESSIBLE UPGRADES AND IN THIS ORDER: |
| | ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF |
| | TRAVEL TO THE ALTERED AREA WILL BE DEEMED |
| | DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE |
| | COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE |
| | PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS |
| | EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF |
| | TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING |
| | AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE |
| | ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING |
| | RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, |
| | ENLARGING TOILET STALLS, INSULATING PIPES, OR |
| | INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS |
| | ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH |
| | AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, |
| | INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT |
| | TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING |
| | AN INACCESSIBLE DRINKING FOUNTAIN. |
| | |
| | 1D) THE SAME PLAN ALSO INDICATES A LOCKER ROOM, WITH |
| | BENCHES, PLEASE SHOW COMPLIANCE WITH THE 2010 FL |
| | ACCESS. CODE 803.1-803.5. |
| | |
| | 2) SHEET 4 OF 4 THE REMODELED RESTROOMS, PLEASE PROVIDE |
| | THE LOCATION OF THESE RESTROOMS WITHIN THE BUILDING AND |
| | ON WHICH FLOOR THEY ARE LOCATED. 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 2A) THE FLOOR PLAN SHOWS GRAB RAILS TO BE USED IN |
| | CONJUNCTION WITH THE WATER CLOSET. THE PLANS LACKS: |
| | 2A)(1) THE LOCATION OF THE SIDE WALL GRAB BAR, ACCESS. |
| | CODE 604.5.1 |
| | 2A)(2) THE LOCATION OF THE REAR WALL GRAB BAR, ACCESS. |
| | CODE 604.5.2. |
| | |
| | 2B) PLEASE PROVIDE COMPLIANCE WITH 2010 FL ACCESS. CODE |
| | 609.8 STRUCTURAL STRENGTH REQUIREMENTS. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | |