| 2014-12-13 10:22:25 | PLAN DENIED | | | 1) REFER TO SECTION 304.11 GUARDS 2010 FBC (M) | | | 2) REFER TO SECTION 401.4.1 INTAKE OPENINGS AND | | | 401.5 INTAKE OPENING PROTECTION. 2010 FBC (M) | | | 3) REFER TO SECTION 501.2.1 LOCATION OF EXHAUST | | | OUTLETS. 2010 FBC (M) | | | 4) REFER TO SECTION 601.4 BALANCED RETURN AIR | | | EXCEPTION # 1. 2010 FBC (M) | | | 5) REFER TO SECTION 503.2.4.4 SHUT OFF DAMPER | | | CONTROLS. 2010 FLORIDA ENERGY CODE | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|