Plan Review Notes
Plan Review Notes For Permit 14110788
Permit Number 14110788
Review Stop E
Sequence Number 1
Notes
Date Text
2014-11-21 09:50:1211/21/2014
 PROJECT: INTERIOR IMPROVEMENTS
 PERMIT#: 14110788
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL
 314 AND 315.
  
 2) OUTLETS INSTALLED IN A FIRE RATED WALL SHAL BE
 INSTALLED SUCH THAT THE REQUIRED FIRE-RESISTANCE WILL
 NOT BE REDUCED. R302.4.2 MEMBRANE PENETRATIONS.
 MEMBRANE PENETRATIONS SHALL COMPLY WITH SECTION
 R302.4.1. WHERE WALLS ARE REQUIRED TO HAVE A
 FIRE-RESISTANCE RATING, RECESSED FIXTURES SHALL BE
 INSTALLED SO THAT THE REQUIRED FIRE-RESISTANCE RATING
 WILL NOT BE REDUCED.
  
 3) METAL FRAMING MEMBERS SHALL BE BONDED TO THE
 EQUIPMENT GROUNDING CONDUCTOR FOR THE CIRCUIT THAT MAY
 ENERGIZE THE FRAMING AND BE SIZED IN ACCORDANCE WITH
 THE NEC TABLE 250.122. FOR THE PURPOSE OF THIS SECTION,
 A GROUNDED METAL OUTLET BOX ATTACHED TO THE FRAMING
 SHALL BE PERMITTED.
  
 4) THE LIGHTS INSTALLED AT THE SECOND FL LANDINGS ARE
 PHOTOCELL CONTROLLED ONLY. THE NEC REQUIRES, AT LEAST
 ONE WALL SWITCH? CONTROLLED LIGHTING OUTLET SHALL BE
 INSTALLED TO PROVIDE ILLUMINATION ON THE EXTERIOR SIDE
 OF OUTDOOR ENTRANCES OR EXITS 210.70 (A)(2)(B)
  
 5) PROVIDE THE REQUIRED CIRCUITING AND DISCONNECTING
 MEANS FOR ALL AHU'S. REVISE PANEL SCEDULES AND LOAD
 CALCULATIONS ACCORDINGLY. NEC 408.4, 440.14, WPB
 AMENDMENTS TO THE FBC 107.3.2
  
 6) EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE
 LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND
 SPECIFIC PURPOSE OR USE. NEC 408.4
  
 7) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16, 110.22
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  