2014-12-17 07:40:44BUILDING PLAN REVIEW
 PERMIT: 14110788
 ADD: 418 25TH ST
 CONT: SOUTHERN COAST
 TEL: (561)584-8502
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. DEC.17/ 2014
 ACTION: DENIED
  
 1) THE COVER SHEET T, UNDER THE HEADING PROJECT DATA,
 THE PLANS DO NOT INDICATE IF THIS IS A FIRE SPRINKLERED
 BUILDING.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING SPRINKLERED OR NON- SPRINKLERED
 FBC-BTABLE 508.4.
  
 2) THIS BUILDING IS A MIXED USE BUILDING THE COVERSHEET
 LIST BUSINESS AND R2. SHEET A-2 SUITE # 105 SHOWS A
 OVER HEAD DOOR IN A LARGE ROOM, NO WORK IS TO OCCUR IN
 THIS AREA BUT THE OCCUPANCY USAGE WILL NEED TO BE
 KNOWN, IS THIS AREA TO BE A S1 OR S2 OCCUPANCY/ WILL IT
 BE USED FOR VEHICLE (AUTOMOBILE) PARKING? FBC-B TABLE
 508.4.
  
 3) AGAIN THE COVER SHEET DOES NOT PROVIDE THE
 HORIZONTAL FIRE RATING BETWEEN OCCUPANCIES, PLEASE
 PROVIDE CODE COMPLIANCE FOR FBC-B 707.3.9. & TABLE
 707.3.9 FOR HORIZONTAL ASSEMBLIES. PLEASE PROVIDE
 DETAIL OR SECTION THRU THE 2ND FLOOR, FLOOR ASSEMBLIES.
 PLEASE SHOW DETAIL ALSO OF A FIRE RATED TENANT
 SEPARATION WALL INTERSECTING THE FLOOR ASEMBLY. IF
 FLOOR TRUSSES THE CONTINUNITY SHOULD GO ALL THE WAY TO
 THE UNDER SIDE OF THE 2ND FLOOR DECK. FBC-B 709.4.
  
 4) SHEET A-2 SHOWS AN EXISTING TENNANT SEPARATION WALL
 BETWEEN ROOM # 104 & SUITE # 105. THE PLANS DO NOT
 IDENTIFY THIS WALL, OR THE WALL FIRE RATING, COMMON
 WALL BETWEEN 2 TENANCIES, AND POSSIBLY 2 OCCUPANCIES?
 PLEASE IDENTIFY WALL AND FIRE RATINGS. 2010 FBC-B 709.6
 / TABLE 508.4.
  
 5) SHEET A2 THE EXTERIOR STAIR SHOWS A DOORWAY BENEATH
 THE STAIRS, PLEASE SHOW HOW A ONE HOUR FIRE RATING
 SEPARATES TTHE STAIRWAY FROM THE USEABLE SPACE BELOW.
 FBC-B 1026.6.
  
 6) SHEET A3 THE PLANS FAIL TO IDENTIFY THE TENANT
 SPERATION WALL AS BEING A FIRE RATED WALL. FBC-B
 709.1.6./ 709.4 CONTINUITY.
  
 7) SHEET A3 THE PLANS DO NOT IDENTIFY IF THE WINDOW AT
 THE EXTERIOR STAIR IS 1 HOUR FIRE RATED NOR THE
 EXTERIOR DOOR OF UNIT A THAT LEADS TO THE EXTERIOR
 STAIRWAY. SEE FBC-B 1019.2. ALSO NOTE ON THE 1ST FLOOR
 SUITE # 105 THE SIDE DOOR IS WITHIN 10 FT OF THE 2ND
 FLOOR LANDING WILL ALSO NEED TO BE A 3/4 HOUR OPENING
 PROTECTIVE.
  
 8) SHEET A3 PLEASE SHOW THAT THE 2 R-2 BEDROOMS HAVE AT
 LEAST (1) WINDOW IN COMPLIANCE WITH FBC-B 1029.2.
  
 9) SHEET A3 DOES NOT SHOW COMPLIANCE WITH F] 907.2.10.2
 AUTOMATIC SMOKE DETECTION SYSTEM.
 AN AUTOMATIC SMOKE DETECTION SYSTEM THAT ACTIVATES THE
 OCCUPANT NOTIFICATION SYSTEM IN ACCORDANCE WITH SECTION
 907.5 SHALL BE INSTALLED IN CORRIDORS, WAITING AREAS
 OPEN TO CORRIDORS AND HABITABLE SPACES OTHER THAN
 SLEEPING UNITS AND KITCHENS.
  
 10) SHEET A4 INDICATES THE USE OF A NEW STOREFRONT
 GLAZYING SYSTEM. PLEASE PROVIDE COMPLIANCE WITH;
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) STOREFRONTS, WALL LOUVERS
  
 11) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC...
  
 12) SHEET A-4 PROVIDES THE WIND DESIGN CRITERIA BUT NOT
 THE POSITIVE AND NEGATIVE PRESSURES FOR THE STOREFRONT
 GLAZING SYSTEM. FBC-B 1609.6.4.41 COMPONENTS &
 CLADDING.
  
 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  