| 2014-11-25 10:43:19 | PERMIT # 14110774 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | PROVISO: ALL TENANT SPACES FOR THE MARKETPLACE MUST BE |
| | TIED INTO THE MASTER FIRE ALARM PANEL FOR THE BUILDING. |
| | EACH TENANT SPACE WILL BE INTERCONNECTED AND UPON |
| | ACTIVATION OF AN ALARM IN ANY ONE SPACE, ALL SPACES |
| | WILL HAVE THEIR NOTIFICATION DEVICES ACTIVATE. AN FACP |
| | IN A TENANT SPACES WILL HAVE THE "RESET" AND "SILENCE" |
| | FUNCTIONS DEACTIVED. RESET AND SILENCE OF AN ALARM IS |
| | LIMITED TO THE MASTER PANEL FOR THE BUILDING AND MAY |
| | ONLY BE DONE BY A LICENSED FIRE ALARM TECHNICIAN. |
| | SHOULD IT BE FOUND THAT TENANTS ARE ACCESSING THE |
| | PANELS IN THE TENANT SPACES AND/OR USING THE "RESET" OR |
| | "SILENCE" FUNCTIONS, THE OFFICE OF THE FIRE MARSHAL MAY |
| | REQUIRE THAT THE TENANT FACP BE REMOVED. |
| | PER APPROVED MASTER PLANS: MAIN FACP FOR THIS BUILDING |
| | IS TO BE THE ONLY PANEL TO NOTIFY THE FIRE DEPARMENT. |
| | NOTIFICATION WILL DESIGNATE SPECIFIC ADDRESS OF TENANT |
| | WHERE TROUBLE IS LOCATED. EACH BUILDING SHALL |
| | ALARM/EVACUATE ONLY THE SPACES IN THAT BUILDING (IE AN |
| | ALARM IN "B" WILL NOT EVACUATE ANY SPACE IN "A", "BII", |
| | OR "C". EACH TENANT SPACE FACP SHALL BE CONNECTED TO |
| | MAIN FACP FOR THIS BUILDING VIA MODULES. TENANT SYSTEM |
| | SHALL BE COMPATIBLE WITH NOTIFIER OR EQUAL APPROVED |
| | MAIN FACP/HARDWARE EACH FLOW/TAMPER SHALL BE ZONED SO |
| | THAT AN ALARM WILL SOUND FOR EACH BUILDING SEPARATELY. |
| | |
| | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE SUBMITTED BY EMAIL ([email protected]) |
| | ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND |
| | APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT |
| | 500 NORTH DIXIE HIGHWAY. |
| | |
| | WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT |
| | SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED |
| | AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE |
| | MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM |
| | SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD |
| | INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY |
| | BE NEEDED. |
| | |