| 2014-12-18 07:31:31 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | PLEASE HAVE THE QUALIFIER CALL ME. THE INSTALLATION |
| | SCHEDULE MAY BE REDLINED FOR ISSUANCE. |
| | |
| | RESUBMITTAL SHEET STATES THAT "A DATED BUT OTHERWISE |
| | UNCHANGED INSTALLATION SCHEDULE ARE ATTACHED." THIS |
| | INSTALLATION SCHEDULE HAD COMMENTS, SEE REVIEW #2. |
| | |
| | TO RECAP - REVIEW 1 DID NOT INCLUDE AN INSTALLATION |
| | SCHEDULE. |
| | |
| | REVIEW 2 - INSTALLATION SCHEDULE SUBMITTED BUT HAD |
| | CORRECTIONS. |
| | |
| | REVIEW 3 - A MARKED PRODUCT APPROVAL WAS SUBMITTED, BUT |
| | A NEW INSTALLATION SCHEDULE WAS NOT PROVIDED. |
| | |
| | REVIEW 4 - THE SAME INSTALLATION SCHEDULE AS REVIEW 2 |
| | WAS SUBMITTED. |
| | |
| | AS EXPEDITED PLAN REVIEW HAS BEEN REQUESTED, IT APPEARS |
| | THAT THERE IS SOME URGENCY FOR THIS PROJECT. PLEASE |
| | HAVE THE QUALIFIER CONTACT ME IF HE WOULD LIKE TO |
| | DISCUSS A REDLINED PLAN FOR ISSUANCE. IF THE QUALIFIER |
| | DOES NOT WISH TO CALL ME, PLEASE SEE COMMENTS FROM |
| | REVIEW #2 AND REVISE THE INSTALLATION SCHEDULE |
| | ACCORDINGLY AND RESUBMIT. |
| | |
| | FOR YOUR CONVENIENCE, COMMENTS FROM REVIEW #2 ARE: |
| | |
| | |
| | 1. FBC 2010 RESIDENTIAL 301, FASTENING PROPOSED DOES |
| | NOT MEET THE REQUIREMENTS OF THE PRODUCT APPROVAL. |
| | |
| | "SHUTTER CONNECTION MOUNTING TYPE" COLUMN ON THE |
| | INSTALLATION SCHEDULE SHOULD CORRELATE WITH THE NAMING |
| | CONVENTION IN THE PRODUCT APPROVAL. SEE SHEETS 14 AND |
| | 15. "WALL MOUNT" IS PROPOSED. ON SHEETS 14 AND 15, |
| | CONNECTION TYPES "H" AND "K" ARE CIRCLED. PLEASE REVISE |
| | THIS COLUMN TO CORRELATE WITH THE PRODUCT APPROVAL. |
| | |
| | 2. CONNECTION TYPE K IS A FLOOR MOUNT AND REQUIRES A |
| | CONCRETE SUBSTRATE. "CONCRETE BLOCK" IS STATED AS THE |
| | SUBSTRATE ON THE INSTALLATION SCHEDULE. A FLOOR IS |
| | TYPICALLY FORMED AND POURED CONCRETE. PLEASE CLARIFY, |
| | OR REVISE EITHER CONNECTION TYPE AND/OR SUBSTRATE. |
| | |
| | 3. THE ITEMS CIRCLED ON THE PRODUCT APPROVAL APPEAR TO |
| | INDICATE CONNECTION TYPE "H" WITH 10" SPACING CIRCLED |
| | AT THE TOP, BUT THIS IS A FLOOR CONNECTION (CAN ONLY BE |
| | USED AT THE FLOOR). |
| | |
| | "K" IS ALSO CIRCLED WITH 7" SPACING, APPEARS TO BE THE |
| | BOTTOM CONNECTION TYPE, SEE ITEM 2 REGARDING SUBSTRATE. |
| | |
| | PROPOSED INSTALLATION IS NOT CLEAR; COMPLIANCE CANNOT |
| | BE DETERMINED. |
| | |
| | |