| 2015-12-07 12:13:16 | |
| | NOTE: |
| | THERE ARE TWO OPTIONS TO EXPEDITE THE PERMIT ISSUANCE: |
| | (1) PERMIT MAY BE ISSUED WITH A PROVISO. OWNER/BUILDER |
| | WILL ADDRESS COMMENTS AFTER THE PERMIT IS ISSUED. FEES |
| | WILL APPLY OR (2)OWNER/BUILDER TO ADDRESS COMMENTS |
| | BEFORE ISSUING THE PERMIT. OWNER/BUILDER TO NOTIFY THIS |
| | OFFICE WITH PREFERRED OPTION. |
| | |
| | |
| | RESIDENTIAL (R3) ADDITION FOURTH BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: 2010 FBC. |
| | |
| | 1- NEW ENERGY CALCULATIONS SUBMITTED: |
| | A) THIS PROJECT WAS IS BEING REVIEWED UNDER THE 2010 |
| | FBC. FORM R405-2014 SUBMITTED IS FOR THE 2014 CODE. |
| | NEED TO PROVIDE FORM FOR 2010 FBC. SEE PLANS AND SEC. |
| | 103.2.1.1.2 OF 2010 FBC- ENERGY CONSERVATION. |
| | |
| | B) CLARIFY WHY SPECIFYING R-3.3 FOR CONCRETE BLOCK WALL |
| | IN ITEM #9(A) IF PLANS CALL FOR R-4.2?. SEC. |
| | 103.2.1.1.2 OF 2010 FBC- ENERGY CONSERVATION. |
| | |
| | C) ITEM #15 IS TAKING THE CROSS VENTILATION CREDIT. |
| | SHOW HOW COMPLYING WITH THE CROSS VENTILATION CREDIT AS |
| | REQUIRED BY SEC. 405.6.4 OF 2010 FBC- ENERGY |
| | CONSERVATION. |
| | |
| | D) WALLS AND WINDOWS ORIENTATION SHOWN ON PAGE 3 OF 4 |
| | DON'T MATCH PLANS. REVISE AS REQUIRED. SEC. 103.2.1.1.2 |
| | OF 2010 FBC- ENERGY CONSERVATION. |
| | |
| | E) NEW FRENCH DOORS BY THE NEW SITTING AREA NEED TO BE |
| | CONSIDERED IN THE GLAZING AREA AS REQUIRED BY SEC. |
| | 405.5.3 OF 2010 FBC- ENERGY CONSERVATION. |
| | |
| | F) WINDOWS OVERHANG DEPTH AND SEPARATION SHOWN ON PAGE |
| | 3 OF 4 DON'T MATCH PLANS. SEC. 103.2.1.1.2 OF 2010 FBC- |
| | ENERGY CONSERVATION. |
| | |
| | FOR YOUR INFORMATION: LABEL FOR WINDOWS AND DOORS |
| | SHOWING THE U-FACTOR AND SHGC FACTOR SPECIFIED ON THE |
| | ENERGY CALCULATIONS ON ITEM #7 WILL BE REQUIRED WHEN |
| | THE ENERGY CALCULATIONS ARE NOT USING THE DEFAULT |
| | FACTOR FOR GLAZING. |
| | |
| | ****PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | |