| 2015-08-10 18:59:20 | RESIDENTIAL (R3) ADDITION THIRD BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: 2010 FBC. |
| | |
| | 1- PROVIDE DETAILS AND SPECIFICATIONS SHOWING |
| | COMPLIANCE WITH THE INSULATION R-VALUE SPECIFIED ON THE |
| | ENERGY CALCULATIONS FOR MASONRY WALLS ON ITEM #9. SEC. |
| | 103.2.2 OF 2010 FBC-ENERGY CONSERVATION. (REPEAT |
| | COMMENT. NOT ADDRESSED). |
| | |
| | ***NOTE: COORDINATE PLANS AND ENERGY CALCULATIONS TO |
| | AVOID CONFLICTS AND MORE UNECESARY DELAYS. |
| | |
| | 2- ENERGY CALCULATIONS SUBMITTED: |
| | A) CLARIFY IF CALCULATIONS ARE DONE FOR THE ENTIRE |
| | HOUSE OR JUST FOR THE ADDITION. INFORMATION SUBMITTED |
| | APPLIES TO ENTIRE HOUSE ON SOME AREAS, BUT ONLY FOR THE |
| | ADDITION IN OTHER AREAS. REVISE AS REQUIRED. PROVIDE |
| | EITHER INFORMATION FOR JUST THE ADDITION OR FOR ENTIRE |
| | HOUSE, BUT DON'T MIX BOTH. SEC. 103.2.2 OF 2010 |
| | FBC-RESIDENTIAL. (REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | B) ENERGY CALCULATIONS ARE MISSING THE GLASS AREA OF |
| | THE SLIDING GLASS DOORS. SEC. 405.5.3 OF 2010 |
| | FBC-ENERGY CONSERVATION. (REPEAT COMMENT. NOT |
| | ADDRESSED). |
| | |
| | C) REVISE THE WINDOWS OVERHANG SEPARATION TO MATCH |
| | PLANS SUBMITTED. SEC. 103.2.2 OF 2010 FBC-ENERGY |
| | CONSERVATION. (REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | D) NEW COMMENTS: A) WHY THE SPACES ON PAGE 2 OF 5 |
| | DOESN'T SPECIFY THE KITCHEN IF SUPPOSEDLY THE |
| | CALCULATIONS ARE FOR ENTIRE HOUSE?. B) WHY THE SECOND |
| | FLOOR IS ON SLAB ON GRADE? SEE FLOORS ON PAGE 2 OF 5. |
| | SEC. 103.2.1.1.1 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | |
| | NOTE: WINDOWS AND DOORS LABELS SHOWING U-FACTOR AND |
| | SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS ON |
| | ITEM #7 WILL BE REQUIRED WHEN NOT DEFAULT FACTORS ARE |
| | USED IN THE CALCULATIONS. |
| | |
| | ****PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | |