| 2015-02-26 09:20:11 | RESIDENTIAL (R3) ADDITION SECOND BUILDING REVIEW |
| | COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- PROVIDE DETAILS AND SPECIFICATIONS SHOWING |
| | COMPLIANCE WITH THE INSULATION R-VALUE SPECIFIED ON THE |
| | ENERGY CALCULATIONS FOR MASONRY WALLS ON ITEM #9. SEC. |
| | 103.2.2 OF 2010 FBC-ENERGY CONSERVATION. (REPEAT |
| | COMMENT. DRAWINGS OR ENERGY CALCULATIONS WERE NOT |
| | REVISED. NOTE: THERE WERE ENERGY CALCULATIONS SUBMITTED |
| | FOR A NEW SINGLE FAMILY RESIDENCE IN MARTIN COUNTY). |
| | |
| | 2- ENERGY CALCULATIONS SUBMITTED ARE FOR A DIFFERENT |
| | PROJECT IN MARTIN COUNTY. THE FOLLOWING ITEMS FORM |
| | PREVIOUS CHECKLIST NEED TO BE ADDRESSED: |
| | |
| | A) CLARIFY IF CALCULATIONS ARE DONE FOR THE ENTIRE |
| | HOUSE OR JUST FOR THE ADDITION. INFORMATION SUBMITTED |
| | APPLIES TO ENTIRE HOUSE ON SOME AREAS, BUT ONLY FOR THE |
| | ADDITION IN OTHER AREAS. REVISE AS REQUIRED. PROVIDE |
| | EITHER INFORMATION FOR JUST THE ADDITION OR FOR ENTIRE |
| | HOUSE, BUT DON'T MIX BOTH. SEC. 103.2.2 OF 2010 |
| | FBC-RESIDENTIAL. |
| | ***NOTE: PROVIDE ONLY THE CALCULATIONS THAT PERTAIN TO |
| | FORM 405-10 TO AVOID CONFUSION OR CONFLICTS. |
| | |
| | B) ENERGY CALCULATIONS ARE MISSING THE GLASS AREA OF |
| | THE SLIDING GLASS DOORS. SEC. 405.5.3 OF 2010 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | C) REVISE THE WINDOWS OVERHANG SEPARATION TO MATCH |
| | PLANS SUBMITTED. SEC. 103.2.2 OF 2010 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | D) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. SEC. |
| | 103.2.3.2 OF 2010 FBC-RESIDENTIAL. |
| | |
| | ****PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | |