2015-02-26 09:20:11RESIDENTIAL (R3) ADDITION SECOND BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE DETAILS AND SPECIFICATIONS SHOWING
 COMPLIANCE WITH THE INSULATION R-VALUE SPECIFIED ON THE
 ENERGY CALCULATIONS FOR MASONRY WALLS ON ITEM #9. SEC.
 103.2.2 OF 2010 FBC-ENERGY CONSERVATION. (REPEAT
 COMMENT. DRAWINGS OR ENERGY CALCULATIONS WERE NOT
 REVISED. NOTE: THERE WERE ENERGY CALCULATIONS SUBMITTED
 FOR A NEW SINGLE FAMILY RESIDENCE IN MARTIN COUNTY).
  
 2- ENERGY CALCULATIONS SUBMITTED ARE FOR A DIFFERENT
 PROJECT IN MARTIN COUNTY. THE FOLLOWING ITEMS FORM
 PREVIOUS CHECKLIST NEED TO BE ADDRESSED:
  
 A) CLARIFY IF CALCULATIONS ARE DONE FOR THE ENTIRE
 HOUSE OR JUST FOR THE ADDITION. INFORMATION SUBMITTED
 APPLIES TO ENTIRE HOUSE ON SOME AREAS, BUT ONLY FOR THE
 ADDITION IN OTHER AREAS. REVISE AS REQUIRED. PROVIDE
 EITHER INFORMATION FOR JUST THE ADDITION OR FOR ENTIRE
 HOUSE, BUT DON'T MIX BOTH. SEC. 103.2.2 OF 2010
 FBC-RESIDENTIAL.
 ***NOTE: PROVIDE ONLY THE CALCULATIONS THAT PERTAIN TO
 FORM 405-10 TO AVOID CONFUSION OR CONFLICTS.
  
 B) ENERGY CALCULATIONS ARE MISSING THE GLASS AREA OF
 THE SLIDING GLASS DOORS. SEC. 405.5.3 OF 2010
 FBC-ENERGY CONSERVATION.
  
 C) REVISE THE WINDOWS OVERHANG SEPARATION TO MATCH
 PLANS SUBMITTED. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 D) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. SEC.
 103.2.3.2 OF 2010 FBC-RESIDENTIAL.
  
 ****PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712