| Plan Review Notes For Permit 14110682 |
| Permit Number |
14110682 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2015-11-12 15:31:24 | BUILDING REVIEW APPROVED WITH PROVISO: | | | | | | 1- SIZE OF FOOTING SPECIFIED ON REVISED SHEET A1 | | | DOESN'T MATCH SIZE SHOWN ON FOOTING SCHEDULE ON SHEET | | | A4. REVISE AS REQUIRED. | | | | | | 2- SHUTTERS INSTALLATION SCHEDULE: REVISE THE ANCHOR | | | SPACING FOR THE CALK-IN ANCHOR SPECIFIED. NEED TO USE | | | THE MASONRY COLUMN NOT THE CONCRETE COLUMN. SEE TABLES | | | ON SHEET 5 AND 6 OF 8 OF THE SHUTTERS PRODUCT APPROVAL | | | SUBMITTED AND REVISE AS REQUIRED. |
|