2015-08-17 18:39:23NEW SINGLE FAMILY RESIDENCE (R3) SECOND MECHANICAL
 REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- EQUIPMENT SIZING CALCULATIONS SUBMITTED DON'T
 IDENTIFY THE PROGRAM THAT WAS ISSUED TO PERFORM THE
 CALCULATIONS. NEED TO USE APPROVED SOFTWARE. SEE SEC.
 403.6 OF 2010 FBC-ENERGY CONSERVATION.
  
 2- EQUIPMENT SIZING CALCULATIONS NEED TO BE DONE BASED
 ON THE BUILDING LOADS FOR THE ACTUAL DIRECTIONAL
 ORIENTATION O THE BUILDING. CALCULATIONS SUBMITTED
 DON'T MATCH ACTUAL BUILDING ORIENTATION. SEE SEC. 403.6
 OF 2010 FBC-ENERGY CONSERVATION.
  