| Plan Review Notes For Permit 14110682 |
| Permit Number |
14110682 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-08-17 18:39:23 | NEW SINGLE FAMILY RESIDENCE (R3) SECOND MECHANICAL | | | REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- EQUIPMENT SIZING CALCULATIONS SUBMITTED DON'T | | | IDENTIFY THE PROGRAM THAT WAS ISSUED TO PERFORM THE | | | CALCULATIONS. NEED TO USE APPROVED SOFTWARE. SEE SEC. | | | 403.6 OF 2010 FBC-ENERGY CONSERVATION. | | | | | | 2- EQUIPMENT SIZING CALCULATIONS NEED TO BE DONE BASED | | | ON THE BUILDING LOADS FOR THE ACTUAL DIRECTIONAL | | | ORIENTATION O THE BUILDING. CALCULATIONS SUBMITTED | | | DON'T MATCH ACTUAL BUILDING ORIENTATION. SEE SEC. 403.6 | | | OF 2010 FBC-ENERGY CONSERVATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|