| Plan Review Notes For Permit 14110682 |
| Permit Number |
14110682 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-12-15 07:20:34 | NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW | | | COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- A/C PLANS TO HAVE THE NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC. | | | 107.2.1 CITY AMENDMENTS TO FBC. | | | | | | 2- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS. ONLY | | | THE EQUIPMENT SUMMARY WAS PROVIDED. SEC. 403.6 OF 2010 | | | FBC-ENERGY CONSERVATION. | | | ***NOTE: MAKE SURE CALCUALTIONS ARE DONE BASED ON THE | | | HOUSE ACTUAL BUILDING ORIENTATION AS REQUIRED BY SEC. | | | 406.6. | | | | | | 3- CALCULATIONS TO PROVIDE THE MANUFACTURER AND MODEL | | | NUMBER SHOWING THE SENSIBLE AND TOTAL COOLING CAPACITY | | | AS REQUIRED BY SEC. 403.6 OF 2010 FBC-ENERGY | | | CONSERVATION. | | | | | | 4- HEATING INFORMATION SHOWN ON THE EQUIPMENT SIZING | | | SIZING CALCULATIONS DOESN'T MATCH INFORMATION SHOWN ON | | | THE ENERGY CALCULATIONS. REVISE AS REQUIRED TO MATCH. | | | SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|