2014-12-15 07:20:34NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- A/C PLANS TO HAVE THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC.
 107.2.1 CITY AMENDMENTS TO FBC.
  
 2- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS. ONLY
 THE EQUIPMENT SUMMARY WAS PROVIDED. SEC. 403.6 OF 2010
 FBC-ENERGY CONSERVATION.
 ***NOTE: MAKE SURE CALCUALTIONS ARE DONE BASED ON THE
 HOUSE ACTUAL BUILDING ORIENTATION AS REQUIRED BY SEC.
 406.6.
  
 3- CALCULATIONS TO PROVIDE THE MANUFACTURER AND MODEL
 NUMBER SHOWING THE SENSIBLE AND TOTAL COOLING CAPACITY
 AS REQUIRED BY SEC. 403.6 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 4- HEATING INFORMATION SHOWN ON THE EQUIPMENT SIZING
 SIZING CALCULATIONS DOESN'T MATCH INFORMATION SHOWN ON
 THE ENERGY CALCULATIONS. REVISE AS REQUIRED TO MATCH.
 SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT