2014-12-16 10:35:571ST REVIEW: FBC 2010
  
 FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10
 FEET OF EACH SLEEPING ROOM.
  
 NEC 210.12B - OUTLETS TO BE AFCI PROTECTED.
  
 NEC 210.52(A)(1)&(2) OUTLET SPACING, IT APPEARS SOME
 POINTS ALONG THE WALL EXCEED 6? FROM AN OUTLET. SEE
 FRONT DOOR ALONG THE WALL TO THE LEFT IN LIVING ROOM.
  
 NEC 210.52(C)(3)-(3) PENINSULAR COUNTERTOP SPACES. AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH
 PENINSULAR COUNTERTOP SPACE WITH A LONG DIMENSION OF
 600 MM (24 IN.) OR GREATER
 AND A SHORT DIMENSION OF 300 MM (12 IN.) OR GREATER. A
 PENINSULAR COUNTERTOP IS MEASURED FROM THE CONNECTING
 EDGE.
  
 NEC 210.52(G) BASEMENTS AND GARAGES. FOR A ONE-FAMILY
 DWELLING THE FOLLOWING PROVISIONS SHALL APPLY: (1) AT
 LEAST ONE RECEPTACLE OUTLET, IN ADDITION TO THOSE FOR
 SPECIFIC EQUIPMENT, SHALL BE INSTALLED IN EACH
 BASEMENT, IN EACH ATTACHED GARAGE, AND IN EACH DETACHED
 GARAGE WITH ELECTRIC POWER.
  
 NEC 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTED
 REQUIRED FOR GARAGE RECEPTACLE.
  
 NEC 406.11- PROVIDE TAMPER RESISTANT RECEPTACLES.
  
  