| Plan Review Notes For Permit 14110682 |
| Permit Number |
14110682 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-12-16 10:35:57 | 1ST REVIEW: FBC 2010 | | | | | | FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 | | | FEET OF EACH SLEEPING ROOM. | | | | | | NEC 210.12B - OUTLETS TO BE AFCI PROTECTED. | | | | | | NEC 210.52(A)(1)&(2) OUTLET SPACING, IT APPEARS SOME | | | POINTS ALONG THE WALL EXCEED 6? FROM AN OUTLET. SEE | | | FRONT DOOR ALONG THE WALL TO THE LEFT IN LIVING ROOM. | | | | | | NEC 210.52(C)(3)-(3) PENINSULAR COUNTERTOP SPACES. AT | | | LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH | | | PENINSULAR COUNTERTOP SPACE WITH A LONG DIMENSION OF | | | 600 MM (24 IN.) OR GREATER | | | AND A SHORT DIMENSION OF 300 MM (12 IN.) OR GREATER. A | | | PENINSULAR COUNTERTOP IS MEASURED FROM THE CONNECTING | | | EDGE. | | | | | | NEC 210.52(G) BASEMENTS AND GARAGES. FOR A ONE-FAMILY | | | DWELLING THE FOLLOWING PROVISIONS SHALL APPLY: (1) AT | | | LEAST ONE RECEPTACLE OUTLET, IN ADDITION TO THOSE FOR | | | SPECIFIC EQUIPMENT, SHALL BE INSTALLED IN EACH | | | BASEMENT, IN EACH ATTACHED GARAGE, AND IN EACH DETACHED | | | GARAGE WITH ELECTRIC POWER. | | | | | | NEC 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTED | | | REQUIRED FOR GARAGE RECEPTACLE. | | | | | | NEC 406.11- PROVIDE TAMPER RESISTANT RECEPTACLES. | | | | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|