Plan Review Notes
Plan Review Notes For Permit 14110665
Permit Number 14110665
Review Stop E
Sequence Number 1
Notes
Date Text
2014-11-26 16:27:4011/26/2014
 PROJECT: AUDI SIGNAGE
 PERMIT#: 14110665
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE PLANS IN ACCORDANCE WITH THE FOLLOWING COMMENTS:
  
 1) NEC 600.5
 EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS
 SHALL BE PROVIDED WITH AT LEAST ONE OUTLET SUPPLIED BY
 A BRANCH CIRCUIT RATED AT LEAST 20 AMPERES THAT
 SUPPLIES NO OTHER LOAD.
  
 2) NEC 600.3 AND 110.3 LISTING.
 ELECTRIC SIGNS, SECTION SIGNS, AND OUTLINE LIGHTING ?
 FIXED, MOBILE, OR PORTABLE ? SHALL BE LISTED AND
 INSTALLED IN CONFORMANCE WITH THAT LISTING, UNLESS
 OTHERWISE APPROVED BY SPECIAL PERMISSION.
  
 3) NEC 600.6(A)(1) LOCATION.
 DISCONNECTS. EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR
 FEEDER CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR
 OUT-LINE LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN
 EXTERNALLY OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL
 OPEN ALL UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN
 OR OUTLINE LIGHTING SYSTEM THAT IT CONTROLS.
  
 4) FBC-E 505.2.4
 ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 SHALL
 HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN
 NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME
 CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES
 SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS
 OF POWER FOR A MINIMUM OF 10 HOURS.
  
 5) NEC 600.4 MARKINGS.
 (A) SIGNS AND OUTLINE LIGHTING SYSTEMS. SIGNS AND
 OUTLINE LIGHTING SYSTEMS SHALL BE MARKED WITH THE
 MANUFACTURER?S NAME, TRADEMARK, OR OTHER MEANS OF
 IDENTIFICATION; AND INPUT VOLTAGE AND CURRENT RATING.
 (B) SIGNS WITH LAMPHOLDERS FOR INCANDESCENT LAMPS.
 SIGNS AND OUTLINE LIGHTING SYSTEMS WITH LAMPHOLDERS FOR
 INCANDESCENT LAMPS SHALL BE MARKED TO INDICATE THE
 MAXIMUM ALLOWABLE LAMP WATTAGE PER LAMPHOLDER. THE
 MARKINGS SHALL BE PERMANENTLY INSTALLED, IN LETTERS AT
 LEAST 6 MM (1?4 IN.) HIGH, AND SHALL BE LOCATED WHERE
 VISIBLE DURING RELAMPING.
 (C) SECTION SIGNS. SECTION SIGNS SHALL BE MARKED TO
 INDICATE THAT FIELD-WIRING AND INSTALLATION
 INSTRUCTIONS ARE REQUIRED. THE ELECTRICAL CONNECTIONS
 TO SAME ARE UNDER A DIFFERENT PERMIT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  