| Plan Review Notes For Permit 14110637 |
| Permit Number |
14110637 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2015-02-09 11:14:58 | PASS PROVISO | | | 1) PROVIDE ENGINEER DETAIL ON CURB TO ROOF TIEDOWN | | | SHOWING TYPE, SIZE AND SPACING OF ANCHORS. | | | PER SECTION 301.12 WIND RESISTANCE FBC (M) 2010 | | | 2) REFER TO SECTION 304.1 GENERAL PROVIDE MANUFACTURERS | | | INSTALLATION INSTRUCTIONS ON AIR CONDITIONING | | | EQUIPMENT. | | | 2010 FBC (M) | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | | | | |
|