| 2014-11-21 08:33:22 | BUILDING PLAN REVIEW |
| | PERMIT: 14110637 |
| | ADD: 477 S. ROSEMARY # 302-328 |
| | CONT: FASTRACK |
| | TEL: (561)722-8848 / JOHN LESH |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. NOV. 21/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) SHEET CS-1 PROJECT DATA, PLEASE PROVIDE THE BUILDING |
| | TYPE OF CONSTRUCTION, THIS MAY EFFECT THE TYPE OF |
| | MATERIALS TO BE PLACED WITHIN THE BUILDING. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 107.3.5 MINIMUM PLAN |
| | REVIEW CRITERIA FOR BUILDINGS |
| | (3) MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED |
| | (SEE TABLE 503). |
| | |
| | 2A) SHEET A1.1 INDICATES ROOMS 324 A BUSINESS LOUNGE & |
| | ROOM 325 KITCHEN, PLEASE PROVIDE THE SQ. FT. AREA OF |
| | EACH AND THE PROPOSED OCCUPANT LOAD. |
| | THIS USAGE AREA APPEARS TO BE AN ASSEMBLY AREA PLEASE |
| | PROVIDE THE SQ. FT AREA OF WHAT APPEARS TO BE AN |
| | ASSEMBLY USAGE TO DETERMINE IF THIS AREA IS TO BE |
| | CLASSIFIED AS AN ACCESSORY OCCUPANCY OR MIXED |
| | OCCUPANCY. PLEASE REVIEW THE 2010 FBC-B 508.2, & |
| | 508.21. |
| | |
| | 2B) IF THIS DOES BECOME A MIXED USE OCCUPANCY THE PLANS |
| | HAVE NOT DECLARED IF THE TENANCY WAS DESIGNED TO |
| | NONSEPARATED OCCUPANCIES (508.3) OR |
| | SEPARATED OCCUPANCIES (508.4). |
| | |
| | 3A) THIS SHEET WITHIN THE KITCHEN SHOWS A STOVE BUT NO |
| | MENTION OF A HOOD IS INDICATED ON THE ARCHITECTURAL NOR |
| | M2.1A. SEE FBC-B 904.2 / 904.2.1 COMMERCIAL HOOD. |
| | PLEASE NOTE PERMIT 02081582 WAS A PERMIT RESIDENTIAL |
| | PERMIT THAT COMBINED UNIT# 326 & 328 TOGETHER. LATER |
| | PERMIT # 04080408 WAS FOR A COMMERCIAL INTERIOR BUILD |
| | OUT OF THIS SPACE EXPIRED!!!!! |
| | |
| | 3B) PLEASE SHOW THE KITCHEN SINK IN ROOM # 325 IN |
| | CONFORMANCE WITH 2010 FBC- ACCESSIBILITY CODE 606.1-5. |
| | |
| | 4) SHEET A-3: |
| | 4A) DETAIL # 1 INDICATES VARIOUS DROP CEILINGS & |
| | SOFFITS, THERE ARE NO DETAILS FOR STUD THICKNESS/ |
| | GAUGE,TYPE OF MATERIAL, SPACING, HOW THE DROPS ARE |
| | GOING TO BE ANCHORED TO THE STRUCTURAL MEMBERS AND WHAT |
| | TYPE OF FINISH AND THICKNESS WILL BE CLADDING THE |
| | STRUCTURES? |
| | 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE: DROPPED |
| | CEILING & SOFFITS |
| | 11. INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING: |
| | INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT) |
| | |
| | 4B) DETAIL # 2 INDICATES THE USE OF ARMSTRON SERPENTINA |
| | WAVE SYSTEM DROPPED CEILINGS, NOTE INDICATES TO PROVIDE |
| | MANUFACTURER SPECS. 107.2.1.3 ADDITONAL INFORMATION IS |
| | REQUIRED. AGAIN WHAT TYPE OF STRUCTURAL MEMBERS ARE |
| | THESE ELEMENTS GOING TO BE SECURED AND WITH WHAT |
| | MATERIAL. |
| | |
| | 4C) NOTE IN DETAIL INDICATES THE USE OF PLYWOOD |
| | BACKING, THIS MAY BE OF CONCEERN IF THIS BUILDING IS |
| | DECLARED EITHER A TYPE I OR II, NOT DECLAED, SEE |
| | COMMENT # 1. |
| | |
| | 4D) SHEET A3 & A4 BOTH INDICATE THE WALL SYSTEMS ARE BY |
| | OTHERS, PLEASE PROVIDE HOW COMPLIANCE WITH 2010 FBC-B |
| | 803.1.1 INTERIOR WALL FINISHES & CEILING FINISHES CAN |
| | BE MET? |
| | |
| | TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO |
| | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA |
| | TUS.ASPX FOR PERMIT STATUS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |