| 2014-11-26 08:23:11 | 1) SUBMIT A WATER RISER FOR REVIEW. WPB AMEND. TO 2010 |
| | FBC SEC. 107.3.5.1.3. |
| | 2) THE SHOWER SHALL HAVE BACKING FOR GRAB BARS |
| | INSTALLED PER THE 2010 FL. ACCESSIBILITY CODE |
| | SEC.608.3. |
| | 3) THE LOCATION OF THE CONTROLS IN THE SHOWER SHALL |
| | COMPLY WITH SEC.608.5 OF THE 2010 FAC. |
| | 4) SHOW THE INSIDE DIMENSIONS OF THE SHOWER (L X W ). |
| | COMPLY WITH2010 FAC SEC.608.2.2, 608.2.3. |
| | 5) SHOW THE REQUIRED CLEAR FLOOR SPACE ON THE PLAN FOR |
| | THE WATER CLOSET AND LAVATORY PER 2010 FAC SECS. 604.3 |
| | & 606.2. |
| | 6) SHT. 1 - SHOW THE HEIGHT OF THE GRAB BARS ABOVE THE |
| | FINISHED FLOOR. COMPLY WITH 2010 FAC SEC.609.4. THE |
| | HEIGHT IS OBSCURED ON THE PLAN BY PRINTING. |
| | 7) SHOW THE LOCATION OF THE TOILET SEAT ABOVE THE |
| | FINISHED FLOOR PER 2010 FAC SEC. 604.4. THE DIMENSION |
| | IS OBSCURED BY PRINTING. |
| | 8) A DRINKING FOUNTAIN IS REQUIRED IN A BUSINESS |
| | OCCUPANCY PER TABLE 403.1 OF THE FL PLUMBING CODE. |
| | INDICATE ON THE PLAN IF THERE IS AN EXISTING DRINKING |
| | FOUNTAIN IN THE BUILDING THAT COMPLIES WITH THE FLORIDA |
| | ACCESSIBILITY CODE. |
| | 9) THE TOILET ROMM APPEARS TO BE LOCATED ON THE 2ND |
| | FLOOR OF THIS BUILDING YET THE PLANS DO NOT NOT SHOW |
| | ANY MEANS OF ACCESS TO THE 2ND FLOOR. THE 2ND FLOOR |
| | OFFICE AND BATHROOM SHALL BE ACCESSIBLE PER THE FAC |
| | SEC.201.1.1, 213.1, 213.2, 213.3.6, AND VERTICAL |
| | ACCESSIBILITY SHALL BE PROVIDED. |
| | |