| | PROJECT: ADDITION 5913 S. DIXIE |
| | PERMIT#: 14110622 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED. |
| | |
| | 1) FBC-WPB AMENDMENTS 107.3.5.1.2. MINIMUM ELECTRICAL |
| | PLAN REVIEW CRITERIA SHALL INCLUDE BUT NOT BE LIMITED |
| | TO THE FOLLOWING: |
| | "SERVICES" A SITE PLAN INDICATING THE LOCATION OF THE |
| | ELECTRICAL UTILITY, DISCONNECT(S) AND PANEL(S). "WIRING |
| | MEATHODS AND MATERIALS" PROVIDE A DETAILED FLOOR PLAN |
| | INDICATING ALL BRANCH CIRCUIT WIRING WITH NUMBERED |
| | CIRCUITRY ON THE FLOOR PLAN AND CEILING PLAN. |
| | |
| | 2) REVISE THE LIGHTING PLAN TO INDICATE COMPLIANCE WITH |
| | THE FBC-E 505.2 |
| | |
| | 3) THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL |
| | BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL |
| | SWITCHES. NEC 700.12(F) REVISE PANEL SCHEDULE AND FLOOR |
| | PLAN TO INDICATE COMPLIANCE. |
| | A.) EMERGENCY LIGHTING SYSTEMS SHALL BE DESIGNED AND |
| | INSTALLED SO THAT THE FAILURE OF ANY INDIVIDUAL |
| | LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF A LAMP, |
| | CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT REQUIRES |
| | EMERGENCY ILLUMINATION. NEC 700.16 REVISE PANEL |
| | SCHEDULE AND FLOOR PLAN TO INDICATE COMPLIANCE. |
| | |
| | 4) SEE BUILDING REVIEW COMENTS. |
| | ONCE A MORE DETAILED SIGNED SEALED SET OF CONSTRUCTION |
| | DOCUMENTS IS SUBMITTED A MORE COMPREHENSIVE REVIEW OF |
| | THE ELECTRICAL SYSTEM CAN BE COMPLETED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |