| Date |
Text |
| 2014-12-15 12:12:23 | 1) ON THE ISOMETRIC DRAWING SHEETS, CLEARLY IDENTIFY |
| | THE SPECIFIC AREAS OF THE FLOOR THAT APPLY TO THE |
| | SPECIFIC ISOMETRIC; E.G.- AREA Q1, Q3, ETC.AND PROVIDE |
| | A PLAN VIEW SHEET NUMBER OR ROOM NUMBERS. THIS WILL |
| | HELP EXPRDITE THE REVIEW. |
| | 2) THE SPECIFICATIONS FOR THE GAS EQUIPMENT SHALL BE |
| | SUBMITTED AT THE TIME OF THE GAS APPLICATION SUBMITTAL. |
| | 3) SHT. P1.02 - COOLING TOWER WATER SHALL NOT DISCHARGE |
| | TO THE SANITARY SYSTEM PER SEC. 90-126 OF THE CITY OF |
| | WPB CODE OF ORDINANCES SEC. 90-126 (5). SEE GRID LINES |
| | G-H AND 1. |
| | 4) SHT.P2.04 - GRID LINES B.1& 17 - SHOWS A FLOOR SINK |
| | TO THE SANITARY AND A FLOOR DRAIN IN THE SAME AREA |
| | DISCHARGING TO THE GREASE WASTE LINE.CLARIFY. |
| | 5) SHT.P2.04 - LOCATION OF FLOOR SINK & FLOOR DRAIN AT |
| | FIXTURES B8 & B11 DO NOT CORRELATE WITH THE KITCHEN AND |
| | BAR ISOMETRIC ON P3.00. SEE GRID LINES A-B & 17 (TO THE |
| | RIGHT OF THE STAIRWELL.) |
| | 6) SHT. P3.00 - IDENTIFY THE GREASY WASTE ISOMETRICS AS |
| | SUCH AND NOT AS SANITARY.WPB AMEND. TO 2010 FBC |
| | 107.2.1. |
| | 7) SHT.P3.00 - THE KITCHEN AND BAR ISOMETRIC SHOWS A 4" |
| | FLOOR DRAIN BY GRID LINES B.1 & 17 BUT IT IS NOT SHOWN |
| | ON SHT. P2.04. |
| | 8) SHT. P3.00 - A HAND SINK (B33) IS SHOWN ON THE |
| | KITCHEN AND BAR ISOMETRIC BUT IS NOT SHOWN ON |
| | SHT.P2.04. SEE GRID LINE 17 BETWEEN A-B. |
| | 9) SHT.P3.01E - IDENTIFY THE 750 GAL. GREASE |
| | INTERCEPTOR ON THE RISER.WPB AMEND. TO 2010 FBC |
| | SEC.107.2.1. |
| | 10) SHT.P3.01E -KEYNOTE #6- CALLS OUT A 1250 GAL. |
| | GREASE INTERCEPTOR BUT IT IS ALSO IDENTIFYING THE |
| | OIL/SAND INTERCEPTOR AS SUCH.CLARIFY. |
| | 11) SHT. P3.00 - RISER #2 - SHOW THE |
| | CONNECTION/CONTINUATION POINT OF THE 4" SANITARY TO THE |
| | LIFT STATION. WPB AMEND. TO 2010 FBC SEC.107.2.1. |
| | 12) SHT. P3.01 - SHT. P3.01 HAS A NOTE ON WATER RISERE |
| | #6 THAT REFERS TO A 4" GREASE WASTE PIPE /CONNECT TO |
| | GREASE TRAP. CLARIFY. |
| | 13) SHT. P3.01G - THE SANITARY ISOMETRIC DOES NOT |
| | CORRELATE WITH THE FLOOR PLAN ON SHT.P103.FLOOR DRAINS |
| | ARE SHOWN ON THE FLOOR PLAN AND NOT ON THE RISER AND |
| | VICE-VERSA, NUMBER OF WATER CLOSETS AND LAVATORIES ON |
| | THE FLOOR PLAN DO NOT MATCH ISOMETRIC, ISOMETRIC FOR |
| | TOILET ROOMS 116, 117,114B AND 114C DO NOT MATCH FLOOR |
| | PLAN. |
| | 14) SHT. P3.01E- SHOWS A WATER CLOSET DRAINING INTO A |
| | 2" LINE. SIZE THE WASTE AND VENT FOR THIS FIXTURE. |
| | 15) SHT. P3.01E - ELEVATOR SUMP RISER NOTE STATES |
| | "ELEVATOR SUMP/TYP. OF 5 BUT ONLY 4 SUMPS ARE SHOWN ON |
| | THE RISER. CLARIFY. |
| | 16) SHT.P3.01E - THE NARRATIVE STATES "REMOVE SUMP FROM |
| | ELEVATOR PIT". BUT THIS IS NOT REFERENCED ON THE |
| | ELEVATOR PIT RISER. CLARIFY. IDENTIFY THE ELEVATOR |
| | NUMBER WHERE THE SUMP WAS REMOVED. |
| | 17) SHT. P3.01F- RISER #4 SHOWS THE CIRCLED NUMBER 1 AS |
| | SHOCK ARRESTORS & THE KEYNOTE STATES IT AS A '2 1/2 " |
| | COLD WATER LINE ABOVE THE CEILING.CLARIFY. |
| | 18) SHT. P3.01G - RISER #2 - SHOW THE CONNECTION POINT |
| | OF THE 4" SOIL STACK. |
| | 19) SHT. 3.00 - RISER #2 - SHOW THE CONNECTION POINT OF |
| | THE 4" SANITARY LINE TO THE LIFT STATION. |
| | 20) SHT. P3.02 - THE GAS LOAD IS LISTED AS 8,361,000 |
| | AND I CALCULATE THE BTU LOAD AS 8,175,000 AND THE LOAD |
| | AT THE METER SHOWS 7,853,000. CLARIFY. |
| | 21) THE LINE TO THE POOL & SPA HEATER IS UNDERSIZED AT |
| | 1 1/2'. THE MAX. BTU LOAD AT 16' ( THE 20' COLUMN MUST |
| | BE USED) IS 1430,000. THIS LINE SHALL BE SIZED TO 2" |
| | PER TABLE 402.4 (2) OF THE 2010 FGC. |
| | 22) SHT. P3.05 - WHAT IS THE 3" FIRE RISER CONNECTING |
| | TO? IDENTIFY THE SHT. NUMBER WHERE THE CONTINUATION CAN |
| | BE FOUND? IDENTIFY THE CONTINUATION POINT FOR THIS |
| | LINE. |
| | 23) SHT. P4.04 - SUBMIT A KEYNOTE LEGEND FOR THE |
| | CIRCLED NUMBER 1 ON THE SANITARY RISERS. |
| | |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |