| Plan Review Notes For Permit 14110621 |
| Permit Number |
14110621 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-01-13 11:48:35 | 1) THE SPECIFICATIONS FOR THE GAS EQUIPMENT SHALL BE | | | SUBMITTED AT THE TIME OF THE GAS APPLICATION SUBMITTAL. | | | 2) SHT. P3.02 - THE GAS LOAD IS LISTED AS 8,361,000 AND | | | I CALCULATE THE BTU LOAD AS 8,175,000 AND THE LOAD AT | | | THE METER SHOWS 7,853,000. CLARIFY. | | | 3).) THE LINE TO THE POOL & SPA HEATER IS UNDERSIZED AT | | | 1 1/2'. THE MAX. BTU LOAD AT 16' ( THE 20' COLUMN MUST | | | BE USED) IS 1430,000. THIS LINE SHALL BE SIZED TO 2" | | | PER TABLE 402.4 (2) OF THE 2010 FGC. |
|