| 2014-12-17 14:29:29 | 600 OKEECHOBEE BOULEVARD - HIGH RISE HOTEL |
| | PERMIT #14050111 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | NOTE: ALL FIRE REVIEW COMMENTS REFERENCE NFPA 101 REFER |
| | TO NFPA 101-THE LIFE SAFETY CODE (2009 EDITION WITH |
| | FLORIDA AMENDMENTS). |
| | |
| | SHEET P0.01: ELEVATOR SUMP PIPING ROUTED THROUGH FIRE |
| | PUMP ROOM. PER NFPA 20 SECTION 5.12.1.1.4, ROOMS |
| | CONTAINING FIRE PUMPS SHALL BE FREE FROM STORAGE AND |
| | PENETRATIONS NOT ESSENTIAL TO THE OPERATION OF THE PUMP |
| | AND RELATED COMPONENTS. |
| | |
| | SHEET P1.02 & P1.06: ROOF DRAIN PIPING ROUTED IN EXIT |
| | STAIR ENCLOSURE ABOVE CEILING. PER SECTION 7.1.3.2.1, |
| | PENETRATIONS INTO, AND OPENINGS THROUGH, AN EXIT |
| | ENCLOSURE ASSEMBLY SHALL BE LIMITED TO DOOR ASSEMBLIES |
| | FROM NORMALLY OCCUPIED SPACES AND CORRIDORS, REQUIRED |
| | EXIT DOOR OPENINGS, ELECTRICAL CONDUIT SERVING THE EXIT |
| | ENCLOSURE, DUCTWORK AND EQUIPMENT NECESSARY FOR |
| | INDEPENDENT STAIR PRESSURIZATION, WATER OR STEAM PIPING |
| | NECESSARY FOR THE HEATING OR COOLING OF THE EXIT |
| | ENCLOSURE, SPRINKLER PIPING, STANDPIPES, AND |
| | PENETRATIONS FOR FIRE ALARM CIRCUITS, WHERE THE |
| | CIRCUITS ARE INSTALLED IN METAL CONDUIT AND THE |
| | PENETRATIONS ARE PROTECTED. |
| | |
| | FIRE PIT (SKY TERRACE) HAS NOT BEEN ACCEPTED OR |
| | REJECTED AT THIS TIME. PRODUCT DATA AND SHOP DRAWINGS |
| | TO BE SUBMITTED BY CONTRACTOR. OPEN FLAMES WILL NEED TO |
| | BE GUARDED AGAINST ACCIDENTAL OR INTENTIONAL CONTACT BY |
| | OCCUPANTS. |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |
| | |
| | |
| | |
| | |
| | |
| | |