2014-12-19 10:47:04ON SHEETS C5.02 AND C5.03, THE SANITARY IS SHOWN
 CONNECTING WITH A 10X6" WYE WITHIN THE FLORIDA AVENUE
 RIGHT-OF-WAY RATHER THAN VIA A SANITARY DOGHOUSE
 MANHOLE AS SHOWN IN THE ENGINEERING DEPARTMENT
 APPROVAL. PLEASE REVISE THE PLANS TO COMPLY WITH THE
 APPROVED CONSTRUCTION PLANS.
  
 THE PLUMBING PLANS APPEAR TO SHOW ONLY ONE DISCHARGE
 POINT FROM THE LIFT STATION, WHICH THEN APPEARS TO BE
 ROUTED THROUGH THE GREASE TRAP. RESTROOM WASTE IS NOT
 TO BE ROUTED THROUGH THE INTERCEPTOR OR SEPARATOR.
  
 PLEASE SHOW WHERE THE PROPOSED ROOF DRAINS WILL TIE
 INTO THE STORM WATER MANAGEMENT SYSTEM.
  