Plan Review Notes
Plan Review Notes For Permit 14110621
Permit Number 14110621
Review Stop E
Sequence Number 1
Notes
Date Text
2015-01-22 11:45:261/22/2015
 PROJECT: WPC CONVENTION CENTER HILTON HOTEL REVISION
 TRACKING #14110621
 PERMIT#: 14050111
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 3RD ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) E1.03
 PROVIDE MANUFACTURER PRODUCT APPROVALS ON WHEEL CHAIR
 LIFT. NEC 110.3(B)
  
 2) E1.03
 VERIFY ANY LIGHT FIXTURE DISTANCE FROM SWIMMING POOL
 WATER?S EDGE. 680.22(C)(1)
  
 3) E1.11
 VERIFY REQUIRED CLEARANCES ABOUT ELECTRICAL EQUIPMENT
 VFD?S DISC?S ETC.. . NEC 110.26
  
 4) E2.00, E2.01, E2.02
 A. KEY NOTES 1 THROUGH 5 ARE BLACKED OUT IN THE KEY
 NOTE SCHEDULE YET STILL CALLED OUT ON THE FLOOR PLAN.
 B. OUTLETS PLACED BEHIND THE BED SHALL BE EQUIPPED WITH
 PROTECTION. NEC 210.60(B)
  
 5) E2.02
 APPLY KEY NOTE 9 TO THE ENTRANCE TO PRESIDENTIAL SUITE
 #1238
  
 6) E3.06, E3.07, E3.08
 VENDING MACHINES TO BE GFI PROTECTED. NEC 422.51
 OUTLETS WITHIN 6? OF A SINK TO BE GFI PROTECTED. NEC
 210.8(B)(5)
 SEPARATE PERMIT APPLICATION(S) WITH SHOP DRAWINGS,
 PRODUCT APPROVALS AND WRITTEN SEQUENCE OF OPERATION ARE
 REQUIRED FOR ALL EXHAUST HOODS.
  
 7) E4.01
 ADD DRAWING KEYNOTE 5 TO EMERGENCY GENERATOR FEEDER
 F-11 FEEDING THE FIRE PUMP CONTROLLER.
 ADD FEEDER SCHEDULE SYMBOL TO ALL FEEDERS ON RISER
 DIAGRAM TO INDICATE PROPER CONDUCTOR SIZING PER NEC
 310.16 AND WPB AMENDMENTS TO FBC 107.3.2
 ADD NOTE AND INDICATE APPLICATION METHOD FOR BUILDING
 SIGNAGE FOR COMPLIANCE WITH FBC-ENERGY 505.2.4
  
 SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR SITE LIGHTING, GENERATORS. HOOD
 EXHAUST, FIRE ALARM, ACCESS CONTROL SYSTEM, SECURITY,
 CCTV, NETWORK, DATA, AND, COMMUNICATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  