| | PROJECT: WPC CONVENTION CENTER HILTON HOTEL REVISION |
| | TRACKING #14110621 |
| | PERMIT#: 14050111 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 3RD ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) E1.03 |
| | PROVIDE MANUFACTURER PRODUCT APPROVALS ON WHEEL CHAIR |
| | LIFT. NEC 110.3(B) |
| | |
| | 2) E1.03 |
| | VERIFY ANY LIGHT FIXTURE DISTANCE FROM SWIMMING POOL |
| | WATER?S EDGE. 680.22(C)(1) |
| | |
| | 3) E1.11 |
| | VERIFY REQUIRED CLEARANCES ABOUT ELECTRICAL EQUIPMENT |
| | VFD?S DISC?S ETC.. . NEC 110.26 |
| | |
| | 4) E2.00, E2.01, E2.02 |
| | A. KEY NOTES 1 THROUGH 5 ARE BLACKED OUT IN THE KEY |
| | NOTE SCHEDULE YET STILL CALLED OUT ON THE FLOOR PLAN. |
| | B. OUTLETS PLACED BEHIND THE BED SHALL BE EQUIPPED WITH |
| | PROTECTION. NEC 210.60(B) |
| | |
| | 5) E2.02 |
| | APPLY KEY NOTE 9 TO THE ENTRANCE TO PRESIDENTIAL SUITE |
| | #1238 |
| | |
| | 6) E3.06, E3.07, E3.08 |
| | VENDING MACHINES TO BE GFI PROTECTED. NEC 422.51 |
| | OUTLETS WITHIN 6? OF A SINK TO BE GFI PROTECTED. NEC |
| | 210.8(B)(5) |
| | SEPARATE PERMIT APPLICATION(S) WITH SHOP DRAWINGS, |
| | PRODUCT APPROVALS AND WRITTEN SEQUENCE OF OPERATION ARE |
| | REQUIRED FOR ALL EXHAUST HOODS. |
| | |
| | 7) E4.01 |
| | ADD DRAWING KEYNOTE 5 TO EMERGENCY GENERATOR FEEDER |
| | F-11 FEEDING THE FIRE PUMP CONTROLLER. |
| | ADD FEEDER SCHEDULE SYMBOL TO ALL FEEDERS ON RISER |
| | DIAGRAM TO INDICATE PROPER CONDUCTOR SIZING PER NEC |
| | 310.16 AND WPB AMENDMENTS TO FBC 107.3.2 |
| | ADD NOTE AND INDICATE APPLICATION METHOD FOR BUILDING |
| | SIGNAGE FOR COMPLIANCE WITH FBC-ENERGY 505.2.4 |
| | |
| | SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | ARE REQUIRED FOR SITE LIGHTING, GENERATORS. HOOD |
| | EXHAUST, FIRE ALARM, ACCESS CONTROL SYSTEM, SECURITY, |
| | CCTV, NETWORK, DATA, AND, COMMUNICATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |