| 2015-01-10 09:01:48 | BUILDING PLAN REVIEW |
| | REVISION: 14110621 |
| | PERMIT:14050621 |
| | ADD: 600 OKEECHOBEE BLVD. |
| | CONT: COASTAL |
| | TEL: ( |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: JAN. 10/ 2015 |
| | ACTION: PROVISO |
| | |
| | BUILDING REVISION APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | 1) SHEETS A4.01, A4.02 & A4.03 ALL INDICATE THROUGH THE |
| | PROVIDED NARRATIVE TO ELIMINATE CONCRETE ENCASED |
| | COLUMNS IN THE PREFUNCTION PERIMETER REV # 8. |
| | THE 2010 FBC-B TABLE 601 REQUIRES THE STRUCTURAL |
| | COLUMNS TO HAVE A 2 HOUR FIRE-RESISTANCE RATING, WITH |
| | THE ELIMINATION OF BEING ENCASED IN CONCRETE HOW DO YOU |
| | ENTEND ON MEETING THIS CODE REQUIREMENT? ALSO SEE 704.2 |
| | COLUMN PROTECTION. |
| | |
| | 2) SHEETS A4.01 & A4.02 BOTH INDICATE THE ELIMINATION |
| | OF MINERAL BOARD FIRE FIRE PROOFING IN LEU OF FIRE |
| | PROOFING SPRAY, THIS CAN NOT BE ASSUMED WHERE THE |
| | MINERAL BOARD IS ELIMINATED AND FIRE PROOFING SPRAY IS |
| | TO BE APPLIED AT WHAT THICKNESS AND FOR HOW MANY HOURS |
| | OF FIRE RATING. NO WHERE ELSE IN THE NARRATIVE DOES IT |
| | GIVE US WHERE WE WILL FIND THIS INFORMATION. 2010 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1, ADMINISTRATION 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 3) SHEET A4.11 STAIRWELLS 1, 2 & 3 ALL SHOW 3 NEW |
| | ELLIMENTS TO EACH OF THE STAIRWELL LANDINGS (2) |
| | CIRCULAR AND (1) AS A RECTANGLE THE NARRATIVE DOES NOT |
| | INDICATE THE USAGE, PLEASE IDENTIFY. PLEASE REVIEW |
| | SECTION: |
| | |
| | 2010 FBC-B 1022.4 PENETRATIONS. PENETRATIONS INTO AND |
| | OPENINGS THROUGH AN EXIT ENCLOSURE ARE PROHIBITED |
| | EXCEPT FOR REQUIRED EXIT DOORS, EQUIPMENT AND DUCTWORK |
| | NECESSARY FOR INDEPENDENT VENTILATION OR |
| | PRESSURIZATION, SPRINKLER PIPING, STANDPIPES, |
| | ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION |
| | SYSTEMS AND ELECTRICAL RACEWAY SERVING THE EXIT |
| | ENCLOSURE AND TERMINATING AT A STEEL BOX NOT EXCEEDING |
| | 16 SQUARE INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE |
| | PROTECTED IN ACCORDANCE WITH SECTION 713. THERE SHALL |
| | BE NO PENETRATIONS OR COMMUNICATION OPENINGS, WHETHER |
| | PROTECTED OR NOT, BETWEEN ADJACENT EXIT ENCLOSURES. |
| | |
| | 4) FIRE HAS COMMENT ON THIS ITEM SHEET P1.06 NOTES 3 & |
| | 4 INDICATE A ROOF DRAIN GOING TO WASTE IN STAIRWELL # |
| | 3, THE PIPE RUNS ABOVE IN THE CEILING SPACE, PLEASE |
| | PROVIDE IF THIS IS A RATED CEILING, IF SO IS IT A 2 HR |
| | FIRE RATED CEILING? PROVIDE CODE COMPLIANCE WITH : |
| | |
| | 2010 FBC-B 1022.4 PENETRATIONS. PENETRATIONS INTO AND |
| | OPENINGS THROUGH AN EXIT ENCLOSURE ARE PROHIBITED |
| | EXCEPT FOR REQUIRED EXIT DOORS, EQUIPMENT AND DUCTWORK |
| | NECESSARY FOR INDEPENDENT VENTILATION OR |
| | PRESSURIZATION, SPRINKLER PIPING, STANDPIPES, |
| | ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION |
| | SYSTEMS AND ELECTRICAL RACEWAY SERVING THE EXIT |
| | ENCLOSURE AND TERMINATING AT A STEEL BOX NOT EXCEEDING |
| | 16 SQUARE INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE |
| | PROTECTED IN ACCORDANCE WITH SECTION 713. THERE SHALL |
| | BE NO PENETRATIONS OR COMMUNICATION OPENINGS, WHETHER |
| | PROTECTED OR NOT, BETWEEN ADJACENT EXIT ENCLOSURES. |
| | |
| | 5) SHEET A14.01 THE NARRATIVE REV. # 8 INDICATES THE |
| | EXTERIOR DOORS TO THE FPL VAULT ARE NOT TO BE 3 HR. |
| | FIRE RATING. THIS IS NOT A CODE REQUIREMENT ENFORCEABLE |
| | BY THE FLORIDA BUILDING CODE OR THE NEC BUT PLEASE |
| | REVIEW THE FPL VAULT REQUIREMENT & AGREEMENT FOR YOUR |
| | PROJECT. |
| | |
| | 6) LIFE SAFETY SHEETS TO SHOW AREA OF RESCUE ASSISTANCE |
| | 2010 FBC-ACCESSIBILITY CODE 207.1. SEE SECTION 1007 OF |
| | THE 2003 IBC 107.6 AREA OF REFUGE. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |