Plan Review Notes
Plan Review Notes For Permit 14110621
Permit Number 14110621
Review Stop B
Sequence Number 1
Notes
Date Text
2015-01-10 09:01:48BUILDING PLAN REVIEW
 REVISION: 14110621
 PERMIT:14050621
 ADD: 600 OKEECHOBEE BLVD.
 CONT: COASTAL
 TEL: (
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: JAN. 10/ 2015
 ACTION: PROVISO
  
 BUILDING REVISION APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) SHEETS A4.01, A4.02 & A4.03 ALL INDICATE THROUGH THE
 PROVIDED NARRATIVE TO ELIMINATE CONCRETE ENCASED
 COLUMNS IN THE PREFUNCTION PERIMETER REV # 8.
 THE 2010 FBC-B TABLE 601 REQUIRES THE STRUCTURAL
 COLUMNS TO HAVE A 2 HOUR FIRE-RESISTANCE RATING, WITH
 THE ELIMINATION OF BEING ENCASED IN CONCRETE HOW DO YOU
 ENTEND ON MEETING THIS CODE REQUIREMENT? ALSO SEE 704.2
 COLUMN PROTECTION.
  
 2) SHEETS A4.01 & A4.02 BOTH INDICATE THE ELIMINATION
 OF MINERAL BOARD FIRE FIRE PROOFING IN LEU OF FIRE
 PROOFING SPRAY, THIS CAN NOT BE ASSUMED WHERE THE
 MINERAL BOARD IS ELIMINATED AND FIRE PROOFING SPRAY IS
 TO BE APPLIED AT WHAT THICKNESS AND FOR HOW MANY HOURS
 OF FIRE RATING. NO WHERE ELSE IN THE NARRATIVE DOES IT
 GIVE US WHERE WE WILL FIND THIS INFORMATION. 2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 3) SHEET A4.11 STAIRWELLS 1, 2 & 3 ALL SHOW 3 NEW
 ELLIMENTS TO EACH OF THE STAIRWELL LANDINGS (2)
 CIRCULAR AND (1) AS A RECTANGLE THE NARRATIVE DOES NOT
 INDICATE THE USAGE, PLEASE IDENTIFY. PLEASE REVIEW
 SECTION:
  
 2010 FBC-B 1022.4 PENETRATIONS. PENETRATIONS INTO AND
 OPENINGS THROUGH AN EXIT ENCLOSURE ARE PROHIBITED
 EXCEPT FOR REQUIRED EXIT DOORS, EQUIPMENT AND DUCTWORK
 NECESSARY FOR INDEPENDENT VENTILATION OR
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 SYSTEMS AND ELECTRICAL RACEWAY SERVING THE EXIT
 ENCLOSURE AND TERMINATING AT A STEEL BOX NOT EXCEEDING
 16 SQUARE INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 713. THERE SHALL
 BE NO PENETRATIONS OR COMMUNICATION OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT EXIT ENCLOSURES.
  
 4) FIRE HAS COMMENT ON THIS ITEM SHEET P1.06 NOTES 3 &
 4 INDICATE A ROOF DRAIN GOING TO WASTE IN STAIRWELL #
 3, THE PIPE RUNS ABOVE IN THE CEILING SPACE, PLEASE
 PROVIDE IF THIS IS A RATED CEILING, IF SO IS IT A 2 HR
 FIRE RATED CEILING? PROVIDE CODE COMPLIANCE WITH :
  
 2010 FBC-B 1022.4 PENETRATIONS. PENETRATIONS INTO AND
 OPENINGS THROUGH AN EXIT ENCLOSURE ARE PROHIBITED
 EXCEPT FOR REQUIRED EXIT DOORS, EQUIPMENT AND DUCTWORK
 NECESSARY FOR INDEPENDENT VENTILATION OR
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 SYSTEMS AND ELECTRICAL RACEWAY SERVING THE EXIT
 ENCLOSURE AND TERMINATING AT A STEEL BOX NOT EXCEEDING
 16 SQUARE INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 713. THERE SHALL
 BE NO PENETRATIONS OR COMMUNICATION OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT EXIT ENCLOSURES.
  
 5) SHEET A14.01 THE NARRATIVE REV. # 8 INDICATES THE
 EXTERIOR DOORS TO THE FPL VAULT ARE NOT TO BE 3 HR.
 FIRE RATING. THIS IS NOT A CODE REQUIREMENT ENFORCEABLE
 BY THE FLORIDA BUILDING CODE OR THE NEC BUT PLEASE
 REVIEW THE FPL VAULT REQUIREMENT & AGREEMENT FOR YOUR
 PROJECT.
  
 6) LIFE SAFETY SHEETS TO SHOW AREA OF RESCUE ASSISTANCE
 2010 FBC-ACCESSIBILITY CODE 207.1. SEE SECTION 1007 OF
 THE 2003 IBC 107.6 AREA OF REFUGE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  