| Plan Review Notes For Permit 14110596 |
| Permit Number |
14110596 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2015-01-27 16:36:29 | PLAN REVIEW COMMENTS | | | | | | 3RD REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | BUILDING | | | | | | 1) THE RAS 117 INFORMATION THAT WAS SUBMITTED IS NOT | | | CLEAR AND APPEARS TO BE INCORRECT. | | | A) THE COMPONENT AND CLADDING PRESSURES FOR THE ROOF | | | AREAS APPEAR TO BE INCORRECT FOR A STRUCTURE LOCATED IN | | | EXPOSURE C WITH 170 MPH VULT. WIND SPEED AND A 24' MEAN | | | ROOF HEIGHT. SPECIFY HOW THESE PRESSURES WERE | | | DETERMINED. PROVIDE ALL CALCULATIONS. FBC - R301.2.1 | | | AND ASCE 7-10 CHAPTER 30. | | | | | | B) PROVIDE THE CALCULATIONS THAT WERE USED TO DETERMINE | | | THE ENHANCED FASTENING FOR THE PERIMETER AND CORNER | | | ROOF AREAS. FBC 107.2.1.3 | | | | | | C) FOR EACH OF THE THREE ROOF ZONES. SPECIFY THE | | | FASTENER SPACING AT THE 3" LAP AND IN THE (TWO OR MORE | | | IF REQUIRED) STAGGERED ROWS IN THE CENTER OF THE | | | SHEETS. | | | | | | 2) RAS 117 SECTION 8.1 STATES THAT THE MINIMUM FASTENER | | | SEPARATION SHALL NOT BE LESS THAN 4 INCHES ON CENTER. | | | THE DOCUMENT FROM JOHN D. BUEROSSE, P.E. STATES THAT | | | THE LAPS SHOULD BE NAILED AT 3" APART IN ZONE 3 |
|