| Plan Review Notes For Permit 14110596 |
| Permit Number |
14110596 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-11-19 10:45:02 | PLAN REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | BUILDING | | | | | | 1) THE RAS 117 INFORMATION THAT WAS SUBMITTED IS NOT | | | CLEAR AND APPEARS TO BE INCORRECT. | | | A) THE COMPONENT AND CLADDING PRESSURES FOR THE ROOF | | | AREAS APPPEAR TO BE TOO LOW FOR A STRUCTURE LOCATED IN | | | EXPOSURE C WITH 170 MPH VULT. WIND SPEED AND A 24' MEAN | | | ROOF HEIGHT. SPECIFY HOW THESE PRESSURES WERE | | | DETERMINED. PROVIDE ALL CALCULATIONS. FBC - R301.2.1 | | | AND ASCE 7-10 CHAPTER 30. | | | | | | B) PROVIDE THE CALCULATIONS THAT WERE USED TO DETERMINE | | | THE ENHANCED FASTENING FOR THE PERIMETER AND CORNER | | | ROOF AREAS. FBC 107.2.1.3 | | | | | | C) SPECIFY THE DIMENSIONS OF THE PERIMETER AND CORNER | | | ROOF AREAS. SHOW THE CALCULATIONS THAT WERE USED TO | | | DETERMINE THEM. FBC 107.2.1.3 | | | | | | 2) THE VALUE FOR THE WORK OF $11,500.00 IS LOW AND HAS | | | BEEN INCREASED TO $15,900.00 BASED ON MARSHALL & SWIFT | | | VALUATION. FBC 109.3 | | | |
|