Plan Review Notes
Plan Review Notes For Permit 14110578
Permit Number 14110578
Review Stop B
Sequence Number 1
Notes
Date Text
2014-11-15 12:17:24PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) SPECIFY THE STRUCTURAL DESIGN CRITERIA ON THE PLANS.
 FBC 1603.1 GENERAL. CONSTRUCTION DOCUMENTS SHALL SHOW
 THE SIZE, SECTION AND RELATIVE LOCATIONS OF STRUCTURAL
 MEMBERS WITH FLOOR LEVELS, COLUMN CENTERS AND OFFSETS
 DIMENSIONED. THE DESIGN LOADS AND OTHER INFORMATION
 PERTINENT TO THE STRUCTURAL DESIGN REQUIRED BY SECTIONS
 1603.1.1 THROUGH 1603.1.9 SHALL BE INDICATED ON THE
 CONSTRUCTION DOCUMENTS.
 EXCEPTION: CONSTRUCTION DOCUMENTS FOR BUILDINGS
 CONSTRUCTED IN ACCORDANCE WITH THE CONVENTIONAL
 LIGHT-FRAME CONSTRUCTION PROVISIONS OF SECTION 2308
 SHALL INDICATE THE FOLLOWING STRUCTURAL DESIGN
 INFORMATION:
 3. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (MPH) (KM/HR) AND NOMINAL DESIGN WIND
 SPEED, VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1 AND WIND EXPOSURE.
  
 2) SPECIFY THE OCCUPANCY TYPE, TYPE OF CONSTRUCTION AND
 RISK CATEGORY ON THE PLANS. FBC 302.1, FBC602.1 AND FBC
 1604.5 RISK CATEGORY.
  
 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE APPROVAL
 DOCUMENTS FOR THE USP CONNECTORS.
  
 3) SHOW THE LOCATIONS AND SIZES OF ALL EXISTING
 OPENINGS IN THE EXTERIOR BEARING WALL THAT IS TO BE
 REPAIRED. FBC 107.2.1 & 1604.2
  
 4) PROVIDE A FRAMING DETAIL OF A TYPICAL WALL OPENING
 WITH THE HEADER TYPE AND SIZE SPECIFIED. FBC 1604.2
  
  