| 2015-05-18 15:51:04 | 5/18/2015 |
| | PROJECT: INTERIOR |
| | PERMIT#: 14110576 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) THE RISER DIAGRAM INDICATES PANEL A AND B FED |
| | DIRECTLY FROM THE SAME METER WITHOUT ANY OVER CURRENT |
| | PROTECTION AND LANDING DIRECTLY INTO MAIN LUG ONLY |
| | PANELS. INDICATE THE REQUIRED DISCONNECTS FOR THE |
| | SERVICE EQUIPMENT. NEC 230.70 |
| | |
| | 2) THE LINE DIAGRAM IS NOT CLEAR AS TO HOW PANEL "A AND |
| | PANEL B ARE TO BE FED. THE RISER DIGRAM INDICATES BOTH |
| | PANELS FED FROM THE SAME METER. PROVIDE A SITE PLAN |
| | INDICATING THE LOCATION OF THE ELECTRICAL SERVICE FOR |
| | THE BUILDING. WPB AMENDMENTS TO THE FBC 107 |
| | |
| | 3) WHERE WALLS OR PARTITIONS ARE REQUIRED TO HAVE A |
| | FIRE-RESISTANCE RATING THE NEW RECEPTACLE OUTLETS SHALL |
| | BE PROTECTED IN COMPLIANCE WITH FBC 713.3.2. |
| | |
| | 4) PROVIDE ADDITIONAL EMERGENCY ILLUMINATION AT THR |
| | EXIT DOORS AS REQUIRED FOR THE MEANS OF EGRESS. NEC |
| | 700.16 |
| | |
| | 5) THE BRANCH CIRCUIT FEEDING THE EXIT AND EMERGENCY |
| | LIGHTS SHALL BE THE SAME BRANCH CIRCUIT AS THAT SERVING |
| | THE NORMAL LIGHTING IN THE AREA AND CONNECTED AHEAD OF |
| | ANY LOCAL SWITCHES. NEC 700.12 |
| | |
| | 6) INDICATE THE REQUIRED TIME CLOCKS FOR THE STORE |
| | FRONT SIGNS. FBC-E 505.2 |
| | |
| | 7) ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH |
| | GROUND FAULT CIRCUIT INTERRUPTER PROTECTION. NEC 422.52 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |