| Date |
Text |
| 2014-12-02 16:32:26 | BUILDING PLAN REVIEW |
| | PERMIT: 14110574 |
| | ADD: 3500 45TH ST |
| | CONT: MIKE MOORE CONSTRUCTION |
| | TEL: (561)301-9468 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. DEC. 02/ 2014 |
| | ACTION: DENIED |
| | |
| | 1A) PLEASE SPECIFY WHAT TYPE OF STORAGE IS GOING TO |
| | OCCUPY THE BACK HALF OF THE TENANT SPACE S1 OR S2. IS |
| | THIS AREA GOING TO STORE VEHICLES REQUIRING FIRE RATED |
| | WALLS? 2010 FBC-B TABLE 508.4. |
| | |
| | 1B) IF THE STORAGE OCCUPANCY IS GOING TO BE FOR |
| | VEHICLES THEN THE WALL TYPE BETWEEN THE BUSINESS & S2 |
| | OCCUPANCY WILL REQUIRE A 1 HOUR FIRE RATED WALL TO THE |
| | ROOFTOP DECK. TABLE 508.4 & OPENING PROTECTIVES SEE |
| | TABLE 715.4. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO |
| | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA |
| | TUS.ASPX FOR PERMIT STATUS. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |