| Plan Review Notes For Permit 14110537 |
| Permit Number |
14110537 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-03-25 12:30:20 | WPB AMENDMENTS. FBC 107.3.2 | | | PROVIDE ADDITIONAL INFORMATION FOR CLARIFICATION. THE | | | ELECTRICAL PLAN PROVIDED IN THIS SUBMITTAL INDICATES | | | ALL SWITCHGEAR AND BRANCH WIRING IS EXSITING. THERE IS | | | NO INDICATION OF NEW WORK. PROVIDE AN ELECTRICAL PLAN | | | THAT INDICATES HOW THE NEW GATE IS CONNECTED TO THE | | | EXISTING WIRING SYSTEM. INCLUDE CONDUIT AND WIRING | | | TYPES AND SIZES. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] |
|