Plan Review Notes
Plan Review Notes For Permit 14110537
Permit Number 14110537
Review Stop B
Sequence Number 1
Notes
Date Text
2014-11-23 14:50:051ST REVIEW: FBC 2010
  
 THE SUBMITTAL DOES NOT PROVIDE INFORMATION NECESSARY TO
 DETERMINE COMPLIANCE WITH APPLICABLE CODES:
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 PROVIDE ATTACHMENT DETAILS OF GATES TO POST OR SHOP
 DRAWING FORM SUPPLIER REVIEWED BY ROBERT S MONSOUR, PE.
  
 PROVIDE LOCATION OF GATE OPERATOR. INDICATE HOW IT IS
 TO BE MOUNTED OR SECURED TO ITS LOCATION. THERE IS
 FOOTING DETAIL INCLUDED, BUT IT IS UNCLEAR WHAT IT IS
 FOR. THE FOOTING DETAIL IS FROM TEM SYSTEMS, INC. AND
 IT NOT ACKNOWLEGED AS DESIGNED OR REVIEWED BY A DESIGN
 PROFESSIONAL AND DOES NOT INCLUDE THE NAME OF THE
 DESIGNER.
  
 FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
 PROVIDE AN ELECTRICAL DESIGN BY A QUALIFIED ELECTRICAL
 DESIGNER TO TO SHOW SOURCE OF POWER, CIRCUITS, WIRING
 METHOD, OCP & GFCI PROTECTION AT A MINIMUM. .
  
 FBC 107.3.5.3 ? PROVIDE A SITE PLAN TO DEMONSTRATE
 LOCATION OF PROPOSED INPROVEMENTS AND ASSOCIATED ACCESS
 DRIVES.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  