| 2014-11-23 14:50:05 | 1ST REVIEW: FBC 2010 |
| | |
| | THE SUBMITTAL DOES NOT PROVIDE INFORMATION NECESSARY TO |
| | DETERMINE COMPLIANCE WITH APPLICABLE CODES: |
| | |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS |
| | SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING |
| | OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND |
| | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, |
| | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE |
| | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO |
| | SECTION 107.3.5). |
| | |
| | PROVIDE ATTACHMENT DETAILS OF GATES TO POST OR SHOP |
| | DRAWING FORM SUPPLIER REVIEWED BY ROBERT S MONSOUR, PE. |
| | |
| | PROVIDE LOCATION OF GATE OPERATOR. INDICATE HOW IT IS |
| | TO BE MOUNTED OR SECURED TO ITS LOCATION. THERE IS |
| | FOOTING DETAIL INCLUDED, BUT IT IS UNCLEAR WHAT IT IS |
| | FOR. THE FOOTING DETAIL IS FROM TEM SYSTEMS, INC. AND |
| | IT NOT ACKNOWLEGED AS DESIGNED OR REVIEWED BY A DESIGN |
| | PROFESSIONAL AND DOES NOT INCLUDE THE NAME OF THE |
| | DESIGNER. |
| | |
| | FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL |
| | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| | DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. |
| | |
| | PROVIDE AN ELECTRICAL DESIGN BY A QUALIFIED ELECTRICAL |
| | DESIGNER TO TO SHOW SOURCE OF POWER, CIRCUITS, WIRING |
| | METHOD, OCP & GFCI PROTECTION AT A MINIMUM. . |
| | |
| | FBC 107.3.5.3 ? PROVIDE A SITE PLAN TO DEMONSTRATE |
| | LOCATION OF PROPOSED INPROVEMENTS AND ASSOCIATED ACCESS |
| | DRIVES. |
| | |
| | |
| | STEVEN KENNEDY, CBO |
| | CHIEF PLANS EXAMINER |