| Plan Review Notes For Permit 14110508 |
| Permit Number |
14110508 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-12-22 06:06:18 | 1) THE DRINKING FOUNTAIN SHALL HAVE A 30' WIDE BY 48' | | | CLEAR FLOOR SPACE CENTERED ON THE UNIT TO ALLOW FOR A | | | FORWARD APPROACH PER THE 2010 FL. ACCESS. CODE | | | SEC.602.2. A TURNING DIAMETER DOES NOT COMPLY. | | | 2) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS/ | | | INSTALLATION MANUALS FOR THE PEDICURE CHAIRS. 2ND | | | REQUEST. WPB AMEND. TO 2010 FBC SEC.107.2.1. | | | 3) PROVISIONS FOR THERMAL EXPANSION SHALL BE INSTALLED | | | ON THE HOT WATER SYSTEM PER THE 2010 FL. PLBG. CODE | | | SEC.607.3. | | | 4) WHERE ARE SHEETS A-1 & A-2? SUBMIT 2 COMPLETE SETS | | | OF PLANS WITH ALL THE SHEETS.WPB AMEND. TO 2010 FBC | | | SEC.107.2.1. | | | 5) SHT. P-1 - THE REFERENCE TO SEPARATE FACILITIES NOT | | | BEING REQUIRED FOR ESTABLISHMENTS THAT SEAT 10 PERSONS | | | OR LESS APPLIES TO FOOD SERVICE ESTABLISHMENTS, NOT | | | BUSINESS OCCUPANCIES. THE CORRECT EXCEPTION IS SEC. | | | 403.2 (3) OF THE 2010 FL. PLUMBING CODE. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|