Plan Review Notes
Plan Review Notes For Permit 14110508
Permit Number 14110508
Review Stop P
Sequence Number 2
Notes
Date Text
2014-12-22 06:06:181) THE DRINKING FOUNTAIN SHALL HAVE A 30' WIDE BY 48'
 CLEAR FLOOR SPACE CENTERED ON THE UNIT TO ALLOW FOR A
 FORWARD APPROACH PER THE 2010 FL. ACCESS. CODE
 SEC.602.2. A TURNING DIAMETER DOES NOT COMPLY.
 2) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS/
 INSTALLATION MANUALS FOR THE PEDICURE CHAIRS. 2ND
 REQUEST. WPB AMEND. TO 2010 FBC SEC.107.2.1.
 3) PROVISIONS FOR THERMAL EXPANSION SHALL BE INSTALLED
 ON THE HOT WATER SYSTEM PER THE 2010 FL. PLBG. CODE
 SEC.607.3.
 4) WHERE ARE SHEETS A-1 & A-2? SUBMIT 2 COMPLETE SETS
 OF PLANS WITH ALL THE SHEETS.WPB AMEND. TO 2010 FBC
 SEC.107.2.1.
 5) SHT. P-1 - THE REFERENCE TO SEPARATE FACILITIES NOT
 BEING REQUIRED FOR ESTABLISHMENTS THAT SEAT 10 PERSONS
 OR LESS APPLIES TO FOOD SERVICE ESTABLISHMENTS, NOT
 BUSINESS OCCUPANCIES. THE CORRECT EXCEPTION IS SEC.
 403.2 (3) OF THE 2010 FL. PLUMBING CODE.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR