Plan Review Notes
Plan Review Notes For Permit 14110508
Permit Number 14110508
Review Stop P
Sequence Number 1
Notes
Date Text
2014-11-25 09:23:20WPB ADMIN. AMEND. TO 201 FBC SEC. 107.2.1.
 1) SUBMIT MANUFACTURER'S SPEC SHEETS / INSTALLATION
 INSTRUCTIONS FOR THE PEDICURE CHAIRS.
 2) A NOTE ON THE PLANS STATES THAT THIS IS A CHANGE IN
 USE. INDICATE THE PREVIOUS USE ON THE PLAN. IF THIS IS
 A CHANGE IN OCCUPANCY THE WORK SHALL COMPLY WITH
 CHAPTER 9 OF THE FL. EXISTING BUILDING CODE.
 3) A DRINKING FOUNTAIN IS REQUIRED. NO FEWER THAN TWO
 DRINKING FOUNTAINS SHALL BE PROVIDED PER THE 2010 FAC
 SEC. 211.2.
 4) THE NEW DRINKING FOUNTAINS SHALL BE SHOWN ON THE
 SANITARY AND WATER RISERS.
 5) THE DRINKING FOUNTAINS SHALL BE PROVIDED WITH CLEAR
 FLOOR SPACE COMPLYING WITH THE 2010 FL. ACCESSIBILITY
 CODE SECS.306 & 602.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  