| Plan Review Notes For Permit 14110508 |
| Permit Number |
14110508 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-11-14 10:55:46 | 11/14/2014 | | | PROJECT: NAIL SALON | | | PERMIT#: 14110508 | | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: PROVISO | | | | | | 1) VERIFY THE INSTALLATION OF NEW OUTLET IN EXISTING | | | FIREWALLS ARE INSTALLED SUCH THAT THE REQUIRED | | | FIRE-RESISTANCE WILL NOT BE REDUCED. FBC 713.3.1 | | | | | | 2) VERIFY BRANCH CIRCUIT FEEDING EMERGENCY AND EXIT | | | LIGHTS SHALL BE THE SAME BRANCH CIRCUIT AS THAT SERVING | | | THE NORMAL LIGHTING IN THE AREA AND CONNECTED AHEAD OF | | | ANY LOCAL SWITCHES. NEC 700.12(F) | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|