Plan Review Notes
Plan Review Notes For Permit 14110491
Permit Number 14110491
Review Stop P
Sequence Number 1
Notes
Date Text
2014-11-13 07:21:53PLUMBING PROVISO:
  
 1) 2010 FBC-P 712.2 VALVES REQUIRED.
 A CHECK VALVE AND A FULL OPEN VALVE LOCATED ON THE
 DISCHARGE SIDE OF THE CHECK VALVE SHALL BE INSTALLED
 IN THE PUMP OR EJECTOR DISCHARGE PIPING BETWEEN THE
 PUMP OR EJECTOR AND THE GRAVITY DRAINAGE SYSTEM.
 ACCESS SHALL BE PROVIDED TO SUCH VALVES. SUCH VALVES
 SHALL BE LOCATED ABOVE THE SUMP COVER REQUIRED
 BY SECTION 712.1 OR, WHERE THE DISCHARGE PIPE FROM THE
 EJECTOR IS BELOW GRADE, THE VALVES SHALL BE ACCESSIBLY
 LOCATED OUTSIDE THE SUMP BELOW GRADE IN AN ACCESS PIT
 WITH A REMOVABLE ACCESS COVER.
  
 2) 2010 FBC-P 712.3.5 EJECTOR CONNECTION TO THE
 DRAINAGE SYSTEM.
 PUMPS CONNECTED TO THE DRAINAGE SYSTEM SHALL CONNECT TO
 THE BUILDING SEWER OR SHALL CONNECT TO A WYE
 FITTING IN THE BUILDING DRAIN A MINIMUM OF 10 FEET
 (3048 MM) FROM THE BASE OF ANY SOIL STACK, WASTE STACK
 OR FIXTURE DRAIN. WHERE THE DISCHARGE LINE CONNECTS
 INTO HORIZONTAL DRAINAGE PIPING, THE CONNECTOR SHALL BE
 MADE THROUGH A WYE FITTING INTO THE TOP OF THE DRAINAGE
 PIPING.
  