| Plan Review Notes For Permit 14110473 |
| Permit Number |
14110473 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-11-23 13:05:51 | 1ST REVIEW: FBC 2010 | | | | | | THE PROPOSED REMOVABLE SCREEN PANEL SHOWN ON SHEET A-5 | | | MAY NOT BE USED LESS THAN 3'0" FROM THE PROPERTY LINE. | | | R302.1 EXTERIOR WALLS. | | | CONSTRUCTION, .......OF EXTERIOR WALLS OF DWELLINGS AND | | | ACCESSORY BUILDINGS SHALL COMPLY WITH TABLE R302.1. | | | WITHIN 3' OF THE PROPERTY LINE MUST BE MINIMUM | | | FIRE-RESISTANCE RATING 1 HOUR-TESTED IN ACCORDANCE WITH | | | ASTM E 119 OR UL 263 WITH EXPOSURE FROM BOTH SIDES | | | EXCEPTIONS: 7. SCREEN ENCLOSURE WALLS OF INSECT | | | SCREENING WITH A MAXIMUM OF 25 PERCENT SOLID FLEXIBLE | | | FINISHES. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|