| Plan Review Notes For Permit 14110465 |
| Permit Number |
14110465 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-11-17 13:15:13 | PLAN DENIED | | | 1) PROVIDE CAN SIZE AND GRILL SIZE ON PLANS | | | 2) PROVIDE CFM ON ALL SUPPLY DROPS | | | 3) PROVIDE EQUIPMENT SCHEDULE ON THE | | | PLAN SHOWING MODEL NUMBERS,VOLTAGE | | | AND SEER ALONG WITH AHRI SHEETS IF | | | EQUIPMENT IS BEING REPLACED. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | | | | | | | | | | | | | | | | | | 2014-11-12 12:32:23 | COULD NOT DELETE ACTIVITY (PLACED MY NAME AS REVIEWER | | | IN ERROR) SEE NEW "M" STOP |
|