| 2014-11-24 13:22:17 | 1) SHT. A-1 - THE TOILET PAPER DISPENSER SHALL BE |
| | LOCATED 7" MIN. AND 9 IN. MAXIMUM IN FRONT OF THE WATER |
| | CLOSET MEASURED TO THE CENTERLINE OF THE DISPENSER. |
| | SHOW ON THE PLANS.2010 FL. ACCESS. CODE SEC. 604.7. |
| | 2) SHT. A-1 - THE SEAT HEIGHT OF A WATER CLOSET ABOVE |
| | THE FINISH FLOOR SHALL BE 17"-19" MAX. SHOW ON THE |
| | PLANS.FAC SEC.604.4 |
| | 3) GRAB BAR BEHIND WATER CLOSET SHALL BE MOUNTED AT |
| | 33"- 36" ABOVE THE FINISH FLOOR PER FAC SEC.609.4. SHOW |
| | ON PLANS. |
| | 4) SHOW THE CLEAR FLOOR SPACE FOR THE DRINKING |
| | FOUNTAINS ON THE PLANS.THE CLEAR FLOOR SPACE SHALL BE |
| | CENTERED ON THE INDIVIDUAL FIXTURE AND NOT BOTH |
| | FIXTURES. THE CLEAR FLOOR SPACE SHALL BE POSITIONED FOR |
| | A FORWARD APPROACH.FAC SEC.602.2. |
| | 5) THE DRINKING FOUNTAINS REQUIRE VENTS PER FPC |
| | SEC,901.201. |
| | 6) FLOOR DRAINS REQUIRE TRAP PRIMERS PER THE 2010 FPC. |
| | 1002.4. |
| | 7) CLEANOUTS ARE REQUIRED IN THE BASE OF ALL STACKS. |
| | PER THE 2010 FPC SEC. 708.3.4. |
| | 8)THE WASTE STACKS FOR THE LAVS ARE SHOWN AS 1 1/2 INCH |
| | UNDERGROUND AND 2" THROUGH THE ROOF, CLARIFY. |
| | 9) A CLEANOUT IS REQUIRED WHERE THE BUILDING DRAIN |
| | MEETS THE BUILDING SEWER PER THE 708.3.5. |
| | 10) SHT.A-3 - AS DRAWN, THE DRINKING FOUNTAINS ARE |
| | DISCHARGING INTO A HORIZONTAL WET VENT WHICH IS NOT |
| | PERMITTED PER SEC.909.1 OF THE FPC. |
| | 11) SHT. A-3 - A 1 1/2 WET VENT CAN ONLY CARRY ONE |
| | DRAINAGE FIXTURE UNIT.AS DRAWN THERE ARE TWO FIXTURE |
| | UNITS ON THE 1 1/2" WET VENT AT THE WOMEN'S RESTROOM. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |