2014-11-18 09:18:15THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE PLAN SHEETS PACKETS WERE INCONSISTENT.
  
 PLEASE PROVIDE THE OCCUPANY CLASSIFICATION. IT APPEARS
 THAT IT IS OF MISED USE.
  
 THE FIRE LINE MAY NEED TO BE APPLIED FOR UNDER A
 SEPARATE PERMIT, PLEASE CONFIRM WITH CONSTRUCTION
 SERVICES.
  
 A LIFE SAFETY PLAN WAS NOT SUBMITTED THAT INCLUDES ALL
 OCCUPANCY LOADS, EXIT PATHS, COOMON PATHS OF TRAVEL,
 EMERGECNY LIGHTS, EXIT SIGNS AND EXITS. ALL EXITS MUST
 LEAD TO A PUBLIC WAY. EXITING INTO A LOCKED SECURED
 PARKING LOT IS NOT A PUBLIC WAY.
  
 A FIRE SPRINKLER PLAN WAS NOT PROVIDED, AN ENGINEERED
 CONCEPTUAL PLAN SHALL BE PROVIDED THAT INCLUDES ALL
 COMMODITIES, STORGAE AND RACK PROTECTION.
  
 A FIRE ALARM WAS NOT PROVIDED, AND ENGINEERED
 CONCEPTUAL PLAN SHALL BE PROVIDED. THE FIRE ALARM
 SYSTEM SHALL BE MONITORED.
  
 A KNOX LOCK KEY SYSTEM, INCLUDING A KNOX BOX AND KNOX
 GATE ACCESS, SHALL BE PROVIDED FOR 24 HOUR EMERGENCY
 ACCESS.