| Plan Review Notes For Permit 14110440 |
| Permit Number |
14110440 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-11-18 09:18:15 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | THE PLAN SHEETS PACKETS WERE INCONSISTENT. | | | | | | PLEASE PROVIDE THE OCCUPANY CLASSIFICATION. IT APPEARS | | | THAT IT IS OF MISED USE. | | | | | | THE FIRE LINE MAY NEED TO BE APPLIED FOR UNDER A | | | SEPARATE PERMIT, PLEASE CONFIRM WITH CONSTRUCTION | | | SERVICES. | | | | | | A LIFE SAFETY PLAN WAS NOT SUBMITTED THAT INCLUDES ALL | | | OCCUPANCY LOADS, EXIT PATHS, COOMON PATHS OF TRAVEL, | | | EMERGECNY LIGHTS, EXIT SIGNS AND EXITS. ALL EXITS MUST | | | LEAD TO A PUBLIC WAY. EXITING INTO A LOCKED SECURED | | | PARKING LOT IS NOT A PUBLIC WAY. | | | | | | A FIRE SPRINKLER PLAN WAS NOT PROVIDED, AN ENGINEERED | | | CONCEPTUAL PLAN SHALL BE PROVIDED THAT INCLUDES ALL | | | COMMODITIES, STORGAE AND RACK PROTECTION. | | | | | | A FIRE ALARM WAS NOT PROVIDED, AND ENGINEERED | | | CONCEPTUAL PLAN SHALL BE PROVIDED. THE FIRE ALARM | | | SYSTEM SHALL BE MONITORED. | | | | | | A KNOX LOCK KEY SYSTEM, INCLUDING A KNOX BOX AND KNOX | | | GATE ACCESS, SHALL BE PROVIDED FOR 24 HOUR EMERGENCY | | | ACCESS. |
|