 PROJECT: GLUE PRODUCTS
 PERMIT#: 14110440
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE THE CIRCUITRY ON THE FLOOR PLAN TO COINCIDE
 WITH THE REQUIRED PANEL SCHEDULE AS WELL AS A RISER
 DIAGRAM AND LOAD CALCULATION. WPB AMENDMENTS ? FBC
 107.3.5.1.2 ELECTRICAL
  
 2) PROVIDE COMPLETE CIRCUIT DIRECTORIES FOR ELECTRICAL
 PANELS. EVERY CIRCUIT SHALL BE LEGIBLY IDENTIFIED AS TO
 ITS CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. NEC
 408.4
  
 3) DRINKING FOUNTAIN REQUIRES A GFI PROTECTED
 RECEPTACLE OUTLET. NEC 422.52
  
 4) INDICATE THE REQUIRED LIGHTING CONTROLS FOR INTERIOR
 AND EXTERIOR ILLUMINATION. LIGHTING SYSTEMS SHALL BE
 PROVIDED WITH CONTROLS AS REQUIRED IN SECTIONS 505.2.1,
 505.2.2, 505.2.3 AND 505.2.4. FBC 505.2 LIGHTING
 CONTROLS (MANDATORY).
  
 5) INDICATE THE REQUIRED LIGHTING ABOUT ELECTRICAL
 EQUIPMENT. ILLUMINATION SHALL BE PROVIDED FOR ALL
 WORKING SPACES ABOUT ELECTRICAL PANELS AND EQUIPMENT.
 NEC 110.34 (D)
  
 6) INDICATE THE REQUIRED WORKING CLEARANCE ABOUT
 ELECTRICAL EQUIPMENT. SUFFICIENT ACCESS AND WORKING
 SPACE SHALL BE PROVIDED AND MAINTAINED ABOUT ALL
 ELECTRICAL EQUIPMENT TO PERMIT READY AND SAFE OPERATION
 AND MAINTENANCE OF SUCH EQUIPMENT. NEC 110.26
  
 7) VERIFY SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16, 110.22
  
 8) INDICATE ALL REQUIRED EMERGENCY ILLUMINATION.
 EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED MEANS
 OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, AND ALL
 OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE REQUIRED
 ILLUMINATION. EMERGENCY LIGHTING SYSTEMS SHALL BE
 DESIGNED AND INSTALLED SO THAT THE FAILURE OF ANY
 INDIVIDUAL LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF
 A LAMP, CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT
 REQUIRES EMERGENCY ILLUMINATION. NEC 700.16
  
 9) PROVIDE THE LOCATION OF ALL MECHANICAL EQUIPMENT
 WITH ASSOCIATED REQUIRED DISCONNECTS AND GFI OUTLETS.
 NEC 210.63, 210.8(A)(3), NEC 440.14
  
 10) INDICATE PROVISIONS FOR THE REQUIRED SIGN CIRCUIT
 AND SHOW WINDOW LIGHTING. NEC 210.62, 600.5(A)
  
 11) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR SITE LIGHTING, GENERATORS. HOOD
 EXHAUST, FIRE ALARM, ACCESS CONTROL SYSTEM, SECURITY,
 CCTV, NETWORK, DATA, AND, COMMUNICATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  