| | PROJECT: GLUE PRODUCTS |
| | PERMIT#: 14110440 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE THE CIRCUITRY ON THE FLOOR PLAN TO COINCIDE |
| | WITH THE REQUIRED PANEL SCHEDULE AS WELL AS A RISER |
| | DIAGRAM AND LOAD CALCULATION. WPB AMENDMENTS ? FBC |
| | 107.3.5.1.2 ELECTRICAL |
| | |
| | 2) PROVIDE COMPLETE CIRCUIT DIRECTORIES FOR ELECTRICAL |
| | PANELS. EVERY CIRCUIT SHALL BE LEGIBLY IDENTIFIED AS TO |
| | ITS CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. NEC |
| | 408.4 |
| | |
| | 3) DRINKING FOUNTAIN REQUIRES A GFI PROTECTED |
| | RECEPTACLE OUTLET. NEC 422.52 |
| | |
| | 4) INDICATE THE REQUIRED LIGHTING CONTROLS FOR INTERIOR |
| | AND EXTERIOR ILLUMINATION. LIGHTING SYSTEMS SHALL BE |
| | PROVIDED WITH CONTROLS AS REQUIRED IN SECTIONS 505.2.1, |
| | 505.2.2, 505.2.3 AND 505.2.4. FBC 505.2 LIGHTING |
| | CONTROLS (MANDATORY). |
| | |
| | 5) INDICATE THE REQUIRED LIGHTING ABOUT ELECTRICAL |
| | EQUIPMENT. ILLUMINATION SHALL BE PROVIDED FOR ALL |
| | WORKING SPACES ABOUT ELECTRICAL PANELS AND EQUIPMENT. |
| | NEC 110.34 (D) |
| | |
| | 6) INDICATE THE REQUIRED WORKING CLEARANCE ABOUT |
| | ELECTRICAL EQUIPMENT. SUFFICIENT ACCESS AND WORKING |
| | SPACE SHALL BE PROVIDED AND MAINTAINED ABOUT ALL |
| | ELECTRICAL EQUIPMENT TO PERMIT READY AND SAFE OPERATION |
| | AND MAINTENANCE OF SUCH EQUIPMENT. NEC 110.26 |
| | |
| | 7) VERIFY SAFETY LABELING FOR ARC FLASH PROTECTION FOR |
| | THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC |
| | 110.16, 110.22 |
| | |
| | 8) INDICATE ALL REQUIRED EMERGENCY ILLUMINATION. |
| | EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED MEANS |
| | OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, AND ALL |
| | OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE REQUIRED |
| | ILLUMINATION. EMERGENCY LIGHTING SYSTEMS SHALL BE |
| | DESIGNED AND INSTALLED SO THAT THE FAILURE OF ANY |
| | INDIVIDUAL LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF |
| | A LAMP, CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT |
| | REQUIRES EMERGENCY ILLUMINATION. NEC 700.16 |
| | |
| | 9) PROVIDE THE LOCATION OF ALL MECHANICAL EQUIPMENT |
| | WITH ASSOCIATED REQUIRED DISCONNECTS AND GFI OUTLETS. |
| | NEC 210.63, 210.8(A)(3), NEC 440.14 |
| | |
| | 10) INDICATE PROVISIONS FOR THE REQUIRED SIGN CIRCUIT |
| | AND SHOW WINDOW LIGHTING. NEC 210.62, 600.5(A) |
| | |
| | 11) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | ARE REQUIRED FOR SITE LIGHTING, GENERATORS. HOOD |
| | EXHAUST, FIRE ALARM, ACCESS CONTROL SYSTEM, SECURITY, |
| | CCTV, NETWORK, DATA, AND, COMMUNICATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |