| 2015-01-06 09:08:51 | 01/06/2015 |
| | PROJECT: VALERO STATION |
| | PERMIT#: 14110435 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 2ND ELECTRICAL PLAN REVIEW RE-ISSUE OF 11090826 |
| | ACTION: APPROVED WITH EXCEPTION |
| | |
| | ADDRESS THE FOLLOWING PRIOR TO FINAL INSPECTIONS. |
| | |
| | 1) REVISE THE SIZE OF THE FUSE SIZE MAIN AND CORRECT |
| | THE AIC RATING INDICATED IN THE SERVICE SUMMARY ON |
| | SHHET E-5. THE LOAD CALCULATION AND RISER DIAGRAM ARE |
| | CONFLICTING. THE TOTAL CALCULATED LOAD IS INDICATED AS |
| | 439AMPS WITH A 600AMP 65K AIC RATED MAIN BREAKER SHOWN |
| | ON THE RISER DIAGRAM. REVISE THE NOTE THAT CALLS FOR A |
| | 200AMP MAIN FUSE AND 10K AIC RATING. NEC 230.79. |
| | |
| | 2)FL SS 526.143(2) |
| | A.) INDICATE METHOD OF COMPLIANCE WITH FL SS THAT |
| | REQUIRE EACH NEWLY CONSTRUCTED OR SUBSTANTIALLY |
| | RENOVATED MOTOR FUEL RETAIL OUTLET BE PREWIRED WITH AN |
| | APPROPRIATE TRANSFER SWITCH, AND CAPABLE OF OPERATING |
| | ALL FUEL PUMPS, DISPENSING EQUIPMENT, LIFESAFETY |
| | SYSTEMS, AND PAYMENT-ACCEPTANCE EQUIPMENT USING AN |
| | ALTERNATE GENERATED POWER SOURCE. INDICATE THE LOCATION |
| | AND TYPE OF ALTERNATE GENERATED POWER SOURCE PROPOSED. |
| | B.) NEC 702. PROVIDE SIGNAGE AND INDICATE LOCATION ON |
| | THE PLANS FOR SIGNAGE AS REQUIRED BY NEC 702.8 |
| | |
| | 3) FBC-E 505.2 LIGHTING CONTROLS (MANDATORY). |
| | LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS |
| | REQUIRED IN SECTIONS 505.2.1, 505.2.2, 505.2.3 AND |
| | 505.2.4. REVISE PLANS TO COMPLY WITH THE FBC -ENERGY, |
| | SECTIONS NOTED FOR CONTROL OF INTERIOR AND EXTERIOR |
| | LIGHTING. |
| | |
| | 4) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | ARE REQUIRED FOR SITE LIGHTING, GENERATORS. FUEL, |
| | CANOPY, FIRE ALARM, ACCESS CONTROL SYSTEM, SECURITY, |
| | CCTV, NETWORK, DATA, AND, COMMUNICATION. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |