Plan Review Notes
Plan Review Notes For Permit 14110435
Permit Number 14110435
Review Stop E
Sequence Number 1
Notes
Date Text
2014-12-15 10:21:5412/15/2014
 PROJECT: VALERO STATION
 PERMIT#: 14110435
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW RE-ISSUE OF 11090826
 ACTION: APPROVED WITH EXCEPTION
  
 ADDRESS THE FOLLOWING PRIOR
 1) REVISE THE SIZE OF THE FUSE SIZE MAIN AND CORRECT
 THE AIC RATING INDICATED IN THE SERVICE SUMMARY ON
 SHHET E-5. THE LOAD CALCULATION AND RISER DIAGRAM ARE
 CONFLICTING. THE TOTAL CALCULATED LOAD IS INDICATED AS
 439AMPS WITH A 600AMP 65K AIC RATED MAIN BREAKER SHOWN
 ON THE RISER DIAGRAM. REVISE THE NOTE THAT CALLS FOR A
 200AMP MAIN FUSE AND 10K AIC RATING. NEC 230.79.
  
 2) FL SS 526.143(2)
 A.) INDICATE MEATHOD OF COMPLIANCE WITH FL SS THAT
 REQUIRE EACH NEWLY CONSTRUCTED OR SUBSTANTIALLY
 RENOVATED MOTOR FUEL RETAIL OUTLET BE PREWIRED WITH AN
 APPROPRIATE TRANSFER SWITCH, AND CAPABLE OF OPERATING
 ALL FUEL PUMPS, DISPENSING EQUIPMENT, LIFESAFETY
 SYSTEMS, AND PAYMENT-ACCEPTANCE EQUIPMENT USING AN
 ALTERNATE GENERATED POWER SOURCE. INDICATE THE LOCATION
 AND TYPE OF ALTERNATE GENERATED POWER SOURCE PROPOSED.
 B.) NEC 702. PROVIDE SIGNAGE AND INDICATE LOCATION ON
 THE PLANS FOR SIGNAGE AS REQUIRED BY NEC 702.8
  
 3) FBC-E 505.2 LIGHTING CONTROLS (MANDATORY).
 LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS
 REQUIRED IN SECTIONS 505.2.1, 505.2.2, 505.2.3 AND
 505.2.4. REVISE PLANS TO COMPLY WITH THE FBC -ENERGY,
 SECTIONS NOTED FOR CONTROL OF INTERIOR AND EXTERIOR
 LIGHTING. FBC-E 505.2
  
 4) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR SITE LIGHTING, GENERATORS. FUEL,
 CANOPY, FIRE ALARM, ACCESS CONTROL SYSTEM, SECURITY,
 CCTV, NETWORK, DATA, AND, COMMUNICATION.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved