2014-11-12 18:13:06PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) THE BEARING WALL ANCHOR DETAIL ON SHEET 2.1 DOES NOT
 SPECIFY THE SPECIFIC SIMPSON ANGLE CLIP TO BE USED TO
 ATTACH THE STUDS TO THE BOTTOM PLATES. NOTE: MOST OF
 THE ANGLE PLATES ARE NOT RATED TO RESIST UPLIFT LOADS.
 THE SIMPSON H4, H2.5A OR SIMILAR CONNECTORS ARE RATED
 FOR BOTH UPLIFT AND LATERAL FORCES. FBC 107.2.1 & FBC-R
 301.1
  
 2) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE PRODUCT
 APPROVALS FOR THE SIMPSON CONNECTORS OR SPECIFY THE
 PRODUCT APPROVAL NUMBER FOR EACH OF THEM ON THE PLANS.
  
  