| Plan Review Notes For Permit 14110432 |
| Permit Number |
14110432 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-11-12 18:13:06 | PLAN REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | BUILDING | | | | | | 1) THE BEARING WALL ANCHOR DETAIL ON SHEET 2.1 DOES NOT | | | SPECIFY THE SPECIFIC SIMPSON ANGLE CLIP TO BE USED TO | | | ATTACH THE STUDS TO THE BOTTOM PLATES. NOTE: MOST OF | | | THE ANGLE PLATES ARE NOT RATED TO RESIST UPLIFT LOADS. | | | THE SIMPSON H4, H2.5A OR SIMILAR CONNECTORS ARE RATED | | | FOR BOTH UPLIFT AND LATERAL FORCES. FBC 107.2.1 & FBC-R | | | 301.1 | | | | | | 2) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 | | | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD. SPECIFICALLY, PROVIDE PRODUCT | | | APPROVALS FOR THE SIMPSON CONNECTORS OR SPECIFY THE | | | PRODUCT APPROVAL NUMBER FOR EACH OF THEM ON THE PLANS. | | | | | | |
|