| 2015-01-07 13:44:29 | 1/7/2015 |
| | PROJECT: CHANGE OF COCCUPANCY TO DAY CARE |
| | PERMIT#: 14110421 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | DUPLICATE COMMENTS: |
| | |
| | 1) FL SS 471, 668.001-668.006, FBC, WPB AMENDMENTS |
| | 107.2.1 |
| | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. |
| | |
| | 2) FBC-WPB AMENDMENTS 107.3.5.1.2 |
| | NO ELECTRICAL PLANS HAVE BEEN SUBMITTED. THE MINIMUM |
| | PLAN REVIEW CRITERIA FOR ELECTRICAL INCLUDES THE |
| | FOLLOWING: |
| | A.) AN ELECTRICAL SERVICE RISER, AND LOAD CALCULATION. |
| | NEC 215.5 |
| | B.) THE ELECTRICAL PANEL CIRCUIT DIRECTORIES, NEC 408.4 |
| | C.) A FLOOR PLAN WITH CIRCUIT NUMBERS TO COINCIDE WITH |
| | THE PANEL CIRCUIT DIRECTORY. FBC-WPB AMENDMENTS 107.3.5 |
| | D.) A LIGHTING FIXTURE SCHEDULE AND LIGHTING PLAN, |
| | FBC-WPB AMENDMENTS 107.3.5 |
| | E.) THE EXIT AND EMERGENCY LIGHTING PLAN PROVIDING AN |
| | ILLUMINATED MEANS OF EGRESS. NEC700.12 |
| | F.) A SIGN CIRCUIT. NEC 600.5 |
| | G.) WIRING METHODS SUITABLE FOR THE ENVIRONMENT. |
| | "ASSEMBLY OCCUPANCY". |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |