| 2015-03-11 10:25:30 | RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING |
| | REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- NEW SHEET #2: SHED ROOF SECTION: |
| | A) ORIGINAL COMMENT: ENGINEER OF RECORD TO PROVIDE |
| | DETAILS AND SPECIFICATIONS SHOWING COMPLIANCE WITH THE |
| | ROOF CROSS VENTILATION AS REQUIRED BY SEC. R806 OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | ***RESPONSE TO REVISED WALL SECTION: 3" X 16" SCREEN |
| | VENTS @ 6'-0" O.C. DON'T PROVIDE CROSS VENTILATION. 2 X |
| | 12 ROOF RAFTERS DON'T ALLOW CROOS VENTILATION. THERE IS |
| | NOT SPACE FOR CROSS VENTILATION. SPECIFIED SCREEN VENTS |
| | ONLY PROVIDE VENTILATION TO THE RAFTERS THAT ARE |
| | LOCATED BETWEEN THE SCREEN VENTS. THE REST OF THE ROOF |
| | IS UNVENTED. REVISE AS REQUIRED. |
| | |
| | B) PRINTING QUALITY ON NEW PAGE 2 IS NOT ACCEPTABLE FOR |
| | RECORDS RETENTION AS REQUIRED BY SECTION SEC. 107.2.1.4 |
| | OF CITY AMENDMENTS TO FBC. THE INFORMATION IS NOT |
| | READABLE. LETTERING IS NOT CLEAR AND THE LETTERING |
| | GUIDE LINES DON'T ALLOW TO READ THE LETTERING. |
| | |
| | 2- ENERGY CALCULATIONS: (REPEAT COMMENT. NOT ADDRESSED |
| | AT ALL). |
| | |
| | ****NOTE: INFORAMTION SHOWN ON PLANS BY THE ENGINEER OF |
| | RECORD AND INFORMATION SHOWN ON THE ENERGY CALCULATIONS |
| | NEED TO MATCH. |
| | |
| | A) ENGINEER WHO PREPARED THE CALCULATIONS TO PROVIDE |
| | NAME, LICENSE NUMBER AS REQUIRED BY CHAPTER 471 FLORIDA |
| | STATUTE. |
| | |
| | B) FORM NEEDS TO BE SIGNED AND DATED BY THE |
| | OWNER/AGENT. SEC. 103.2.3 OF 2010 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | C) PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF |
| | FORM. THE CONTRACTOR IS NOT THE OWNER. REVISE AS |
| | REQUIRED. AND, COMPLETE THE PERMIT OFFICE AND |
| | JURISDICTION NUMBER. SEC. 103.2 OF 2010 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | D) REVISE THE ROOF MATERIAL SHOWN ON PAGE 2 OF 5. THERE |
| | ARE NOT SHINGLES ON THIS HOUSE. SEC. 103.2.2 OF 2010 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | E) REVISE THE DOOR INFORMATION SHOWN ON PAGE 3 OF 5. |
| | THERE ARE NOT WOOD DOORS. THERE ARE NOT 3 EXTERIOR |
| | DOORS EITHER. REVISE THE DOOR ORIENTATION. SEE PLANS |
| | AND PRODUCT APPROVALS AND REVISE AS REQUIRED. SEC. |
| | 103.2.2 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | F) REVISE THE WINDOWS INFORMATION SHOWN ON PAGE 3 OF 5. |
| | REVISE THE ORIENTATION TO MATCH PLANS. REVISE THE |
| | OVERHANG DEPTH AND SEPARATION TO MATCH PLANS. SEC. |
| | 103.2.2 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | 3- PROVIDE MANUFACTURER SPECS FOR WINDOWS AND DOORS |
| | SHOWING THE U-FACTOR AND SHGC FACTORS SHOWN ON ITEM # 7 |
| | OF THE ENERGY CALCULATIONS SUBMITTED. SEC. 103.2.2 OF |
| | 2010 FBC-ENERGY CONSERVATION. (REPEAT COMMENT. NOT |
| | ADDRESSED). |
| | ***NOTE: THIS ITEM IS NOT REQUIRED TO BE SUBMITTED NOW. |
| | THIS ITEM WAS REQUESTED TO AVOID ANY CONFLICT WITH THE |
| | ENERGY CALCULATIONS SUBMITTED. IF THE INSTALLED |
| | WINDOWS/DOORS DON'T HAVE THESE ENERGY EFFICIENCY |
| | FACTORS, THEN IT WILL FAIL INSPECTIONS. |
| | |
| | 4- ENGINEER OF RECORD TO PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS FOR MASONRY WALLS SHOWING COMPLIANCE |
| | WITH THE R VALUE SPECIFIED ON ITEM #9. SEC. 103.2.2 OF |
| | 2010 FBC-ENERGY CONSERVATION. (REPEAT COMMENT. NOT |
| | ADDRESSED) |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | *** PLEASE REPLACE AND REMOVE ANY REVISED DRAWING. |
| | SUBMITT OLD/VOID DRAWINGS FOR REFERENCE AND TO EXPEDITE |
| | THE REVIEW PROCESS. |
| | |