2015-03-11 10:25:30RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING
 REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- NEW SHEET #2: SHED ROOF SECTION:
 A) ORIGINAL COMMENT: ENGINEER OF RECORD TO PROVIDE
 DETAILS AND SPECIFICATIONS SHOWING COMPLIANCE WITH THE
 ROOF CROSS VENTILATION AS REQUIRED BY SEC. R806 OF 2010
 FBC-RESIDENTIAL.
  
 ***RESPONSE TO REVISED WALL SECTION: 3" X 16" SCREEN
 VENTS @ 6'-0" O.C. DON'T PROVIDE CROSS VENTILATION. 2 X
 12 ROOF RAFTERS DON'T ALLOW CROOS VENTILATION. THERE IS
 NOT SPACE FOR CROSS VENTILATION. SPECIFIED SCREEN VENTS
 ONLY PROVIDE VENTILATION TO THE RAFTERS THAT ARE
 LOCATED BETWEEN THE SCREEN VENTS. THE REST OF THE ROOF
 IS UNVENTED. REVISE AS REQUIRED.
  
 B) PRINTING QUALITY ON NEW PAGE 2 IS NOT ACCEPTABLE FOR
 RECORDS RETENTION AS REQUIRED BY SECTION SEC. 107.2.1.4
 OF CITY AMENDMENTS TO FBC. THE INFORMATION IS NOT
 READABLE. LETTERING IS NOT CLEAR AND THE LETTERING
 GUIDE LINES DON'T ALLOW TO READ THE LETTERING.
  
 2- ENERGY CALCULATIONS: (REPEAT COMMENT. NOT ADDRESSED
 AT ALL).
  
 ****NOTE: INFORAMTION SHOWN ON PLANS BY THE ENGINEER OF
 RECORD AND INFORMATION SHOWN ON THE ENERGY CALCULATIONS
 NEED TO MATCH.
  
 A) ENGINEER WHO PREPARED THE CALCULATIONS TO PROVIDE
 NAME, LICENSE NUMBER AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTE.
  
 B) FORM NEEDS TO BE SIGNED AND DATED BY THE
 OWNER/AGENT. SEC. 103.2.3 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 C) PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. THE CONTRACTOR IS NOT THE OWNER. REVISE AS
 REQUIRED. AND, COMPLETE THE PERMIT OFFICE AND
 JURISDICTION NUMBER. SEC. 103.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 D) REVISE THE ROOF MATERIAL SHOWN ON PAGE 2 OF 5. THERE
 ARE NOT SHINGLES ON THIS HOUSE. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 E) REVISE THE DOOR INFORMATION SHOWN ON PAGE 3 OF 5.
 THERE ARE NOT WOOD DOORS. THERE ARE NOT 3 EXTERIOR
 DOORS EITHER. REVISE THE DOOR ORIENTATION. SEE PLANS
 AND PRODUCT APPROVALS AND REVISE AS REQUIRED. SEC.
 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 F) REVISE THE WINDOWS INFORMATION SHOWN ON PAGE 3 OF 5.
 REVISE THE ORIENTATION TO MATCH PLANS. REVISE THE
 OVERHANG DEPTH AND SEPARATION TO MATCH PLANS. SEC.
 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 3- PROVIDE MANUFACTURER SPECS FOR WINDOWS AND DOORS
 SHOWING THE U-FACTOR AND SHGC FACTORS SHOWN ON ITEM # 7
 OF THE ENERGY CALCULATIONS SUBMITTED. SEC. 103.2.2 OF
 2010 FBC-ENERGY CONSERVATION. (REPEAT COMMENT. NOT
 ADDRESSED).
 ***NOTE: THIS ITEM IS NOT REQUIRED TO BE SUBMITTED NOW.
 THIS ITEM WAS REQUESTED TO AVOID ANY CONFLICT WITH THE
 ENERGY CALCULATIONS SUBMITTED. IF THE INSTALLED
 WINDOWS/DOORS DON'T HAVE THESE ENERGY EFFICIENCY
 FACTORS, THEN IT WILL FAIL INSPECTIONS.
  
 4- ENGINEER OF RECORD TO PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR MASONRY WALLS SHOWING COMPLIANCE
 WITH THE R VALUE SPECIFIED ON ITEM #9. SEC. 103.2.2 OF
 2010 FBC-ENERGY CONSERVATION. (REPEAT COMMENT. NOT
 ADDRESSED)
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 *** PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
 SUBMITT OLD/VOID DRAWINGS FOR REFERENCE AND TO EXPEDITE
 THE REVIEW PROCESS.
  