| 2014-11-21 11:17:34 | 6651 NORTH JOG ROAD - LIVING WALLS | | | PERMIT #14110377 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | A FIRE HYDRANT IS LOCATED TO THE NORTHWEST OF THE FIRE | | | PUMP ROOM. VERIFY LIVING WALLS DO NOT ENCROACH WORKING | | | CLEARANCES REQUIRED FOR FIRE HYDRANTS. PER SECTION | | | 18.3.4.1 (NFPA 1), FIRE HYDRANTS SHALL BE PROVIDED WITH | | | CLEARANCES OF 7?-6? TO THE FRONT AND SIDES AND 4?-0? TO | | | THE BACKSIDE OF THE STEAMER CAP. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | | | | | | | | | | |
|