Plan Review Notes
Plan Review Notes For Permit 14110349
Permit Number 14110349
Review Stop P
Sequence Number 1
Notes
Date Text
2014-11-13 10:27:35WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 1) INDICATE ON THE PLAN IF THE HANDICAPPED ACCESSIBILE
 TOILET ROOM IS NEW OR EXISTING.
 2) INDDICATE ON THE PLAN WHAT IS EXISTING TO REMAIN AND
 WHAT WILL BE NEW.
 3) THE POSITIONING OF THE SIDE WALL GRAB BAR IN THE
 ACCESSIBLE TOILET ROOM SHALL COMPLY W/ THE 2010 FL.
 ACCESSIBILITY CODE SEC. 604.5.1. SEE FIGURE 604.5.1.
 4) LIST THE OCCUPANCY TYPE ON THE PLAN IN ACCORDANCE W/
 CHAPTER 3 OF THE 2010 FBC.
 5) WATER PIPING EXPOSED TO CONCRETE OR PASSING THRU
 CONCRETE SHALL BE PROTECTED AGAINST EXTERNAL CORROSION
 IN ACCORDANCE WITH 2010 FL. PLUMBING CODE SEC. 305.1,
 305.2, 305.5, & 303.2.
 6) THE SANITARY RISER IS NOT DRAWN TO CODE. THE
 FIXTURES THE SINKS SHALL BE VENTED PER SEC.901.2,
 901.2.1.
 7) SUBMIT MANUF. SPEC SHEETS FOR THE AVERY BACKWASH
 SHAMPOO SYSTEM.
 8) THE SANITARY RISER SHOWS 2 SINKS AND THE FLOOR PLAN
 SHOWS 3. CLARIFY.
 9) IDENTIFY ON THE PLANS WHAT THE LOFT AREA WILL BE
 USED FOR.VERTICAL ACCESSIBILITY MAY BE REQUIRED PER THE
 2010 FL. ACCESSIBILITY CODE SEC.201.1.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  