Plan Review Notes
Plan Review Notes For Permit 14110349
Permit Number 14110349
Review Stop E
Sequence Number 1
Notes
Date Text
2014-11-12 15:54:5411/12/2014
 PROJECT: BEAUTY LOFT
 PERMIT#: 14110349
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE PANEL SCHEDULE AND LOAD CALCULATION TO
 INDICATE NEW AND EXISTING LOADS. WPB AMENDMENTS TO THE
 FBC 107.3.2
  
 2) REVISE FLOOR PLAN TO INDICATE CIRCUIT NUMBERS ON THE
 NEW AND EXISTING CIRCUITS. WPB AMENDMENTS TO THE FBC
 107.3.2
  
 3) REVISE LIGHTING PLAN TO INDICATE THE CIRCUITS TO
 FEED EMERGENCY AND EXIT LIGHTING. EMERGENCY EXIT
 CIRCUIT SHALL BE THE SAME BRANCH CIRCUIT AS THAT
 SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED
 AHEAD OF ANY LOCAL SWITCHES. NEC 700.12(F)
  
 4) INDICATE ON THE REVISED LIGHTING PLAN TH REQUIRED
 EMERGENCY EGRESS LIGHTING AT STAIRS. NEC 700.16
  
 5) PROVIDE MANUFACTURER PRODUCT DATA SHEETS FOR CEILING
 MOUNTED BLOW DRYER SYSTEMS. NEC 110.3(B)
  
 6) INDICATE THE REQUIRED LIGHTING CONTROL ON REVISED
 LIGHTING PLAN. FBC-E 505.2
  
 7) VERIFY WHERE WALLS OR PARTITIONS ARE REQUIRED TO
 HAVE A FIRE-RESISTANCE RATING, RECESSED OUTLETS SHALL
 BE INSTALLED SUCH THAT THE REQUIRED FIRE-RESISTANCE
 WILL NOT BE REDUCED. FBC 713.3.2
  
 8) VERIFY THE REQUIRED SIGN CIRCUIT AND INCLUDE IT IN
 THE REVISED PANEL SCHEDULE. INDICATE COMPLIANCE WITH
 THE FBC-E, 505.20
  
 9) A SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 REQUIRED FOR FIRE ALARM, SECURITY, CCTV, ACCESS CONTROL
 SYSTEM, ETC..
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  