| 2014-11-12 15:54:54 | 11/12/2014 |
| | PROJECT: BEAUTY LOFT |
| | PERMIT#: 14110349 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE PANEL SCHEDULE AND LOAD CALCULATION TO |
| | INDICATE NEW AND EXISTING LOADS. WPB AMENDMENTS TO THE |
| | FBC 107.3.2 |
| | |
| | 2) REVISE FLOOR PLAN TO INDICATE CIRCUIT NUMBERS ON THE |
| | NEW AND EXISTING CIRCUITS. WPB AMENDMENTS TO THE FBC |
| | 107.3.2 |
| | |
| | 3) REVISE LIGHTING PLAN TO INDICATE THE CIRCUITS TO |
| | FEED EMERGENCY AND EXIT LIGHTING. EMERGENCY EXIT |
| | CIRCUIT SHALL BE THE SAME BRANCH CIRCUIT AS THAT |
| | SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED |
| | AHEAD OF ANY LOCAL SWITCHES. NEC 700.12(F) |
| | |
| | 4) INDICATE ON THE REVISED LIGHTING PLAN TH REQUIRED |
| | EMERGENCY EGRESS LIGHTING AT STAIRS. NEC 700.16 |
| | |
| | 5) PROVIDE MANUFACTURER PRODUCT DATA SHEETS FOR CEILING |
| | MOUNTED BLOW DRYER SYSTEMS. NEC 110.3(B) |
| | |
| | 6) INDICATE THE REQUIRED LIGHTING CONTROL ON REVISED |
| | LIGHTING PLAN. FBC-E 505.2 |
| | |
| | 7) VERIFY WHERE WALLS OR PARTITIONS ARE REQUIRED TO |
| | HAVE A FIRE-RESISTANCE RATING, RECESSED OUTLETS SHALL |
| | BE INSTALLED SUCH THAT THE REQUIRED FIRE-RESISTANCE |
| | WILL NOT BE REDUCED. FBC 713.3.2 |
| | |
| | 8) VERIFY THE REQUIRED SIGN CIRCUIT AND INCLUDE IT IN |
| | THE REVISED PANEL SCHEDULE. INDICATE COMPLIANCE WITH |
| | THE FBC-E, 505.20 |
| | |
| | 9) A SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | REQUIRED FOR FIRE ALARM, SECURITY, CCTV, ACCESS CONTROL |
| | SYSTEM, ETC.. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |